External Dimensions And Part Names; Indications Of Leds - Mitsubishi Electric FX3U-128ASL-M User Manual

Melsec-f fx3u
Table of Contents

Advertisement

FX
-128ASL-M User's Manual
3U
1.2

External Dimensions and Part Names

2-4.5 mounting holes
[2]
[3]
[1]
4 (0.16")
43 (1.7")
[1]
Extension cable
[2]
Direct mounting hole
2 holes of φ4.5 (0.18")
(mounting screw: M4 screw)
[3]
Power LED (green)
[4]
Status LEDs (green, red)
[5]
Nameplate
[6]
DIN rail mounting groove (DIN rail: DIN46277,
35 mm (1.38") width)
1.3

Indications of LEDs

LED
Name
display
Module operation
POWER
display
Transmission
LINK
display
Address detection
SET
in progress
display
Transmission
ALM
alarm display
[5]
[6]
[7]
[4]
87 (3.43")
95.5 (3.76")
Unit: mm (inches)
MASS (Weight): Approx. 0.2 kg (0.44 lbs)
[7]
[8]
[9]
[10]
→ Refer to Section 1.3.
[11]
LED
Status
color
ON
Green
OFF
ON
Green
Flicker
OFF
ON
Green
Flicker
OFF
ON
Slow flicker
(one-second intervals)
Red
Fast flicker
(0.2-second intervals)
OFF
1.2 External Dimensions and Part Names
[Without top cover]
[8]
[9]
[10]
9 (0.36")
[11]
DIN rail mounting hook
SET switch
(Automatic address setting switch)
Transmission points number setting switch
(Rotary switch)
Extension connector
AnyWireASLINK connection terminal block
→ Refer to Section 1.4.
Description
5 V DC is being supplied from the PLC.
5 V DC is not being supplied from the PLC, or they are the units failure.
units failure
Operating normally
5 V DC power OFF or the units failure.
Automatic address detection in progress.
Writing in the EEPROM
Operating normally
DP/DN disconnection
DP/DN short
24 V DC is not being supplied or the voltage is low.
Operating normally
1 Introduction