3 Electrical Installation
Control Circuit Terminal Functions
Type
No.
Multi-function input 1 (Closed: Forward run, Open:
S1
Stop)
Multi-function input 2 (Closed: Reverse run, Open:
S2
Stop)
Multi-function input 3 (External fault, N.O.)
S3
Multi-function input 4 (Fault reset)
S4
Multi-function input 5 (Multi-step speed reference 1)
S5
Multi-Function
Multi-function input 6 (Multi-step speed reference 2)
S6
Digital Inputs
Multi-function input 7 (Jog reference)
S7
Multi-function input 8 (External baseblock)
S8
Multi-function input common
SC
SN
Multi-function input 0 V
SP
Multi-function input 24 Vdc
Safe Disable input 1
H1
Safe Disable
Safe Disable input 2
H2
Inputs
Safe Disable function common
HC
Multi-function pulse train input (Frequency reference)
RP
Power supply for analog inputs
+V
Power supply for analog inputs
-V
Multi-function analog input 1 (Frequency reference
A1
bias)
Analog Inputs /
Pulse Train
Input
Multi-function analog input 2 (Frequency reference
A2
bias)
Multi-function analog input 3 / PTC Input (Auxiliary
A3
frequency reference)
Frequency reference common
AC
E (G) Ground for shielded lines and option cards
N.O.
MA
Fault Relay
MB
N.C. output
Fault output common
MC
M1
Multi-function digital output (During run)
M2
Multi-Function
M3
Multi-function digital output (Zero speed)
Digital Output
M4
M5
Multi-function digital output (Speed agree 1)
M6
EN 20
Terminal Name (Function)
YASKAWA Europe TOEP C710616 88A - AC Drive A1000 IP23/54 Floor Standing - Quick Start Guide
Function (Signal Level) Default Setting
Photocoupler
24 Vdc, 8 mA
Use the wire link between terminals SC and SN or SC and SP
to select between sinking, sourcing mode, and the power
supply.
24 V DC power supply for digital inputs, 150 mA max (if no
digital input option DI-A3 is used)
Never short terminals SP and SN as doing so will damage the
drive.
24 V DC, 8 mA
One or both open: Drive output disabled
Both closed: Normal operation
Internal impedance: 3.3 k
Off time of at least 1 ms
Disconnect the wire jumpers shorting terminals H1, H2, and
HC to use the Safe Disable inputs. Set the S3 jumper to select
between sinking, sourcing mode, and the power supply.
Safe disable function common
Input frequency range: 0 to 32 kHz
Signal Duty Cycle: 30 to 70%
High level: 3.5 to 13.2 Vdc, low level: 0.0 to 0.8 Vdc
Input impedance: 3 k
10.5 Vdc (max allowable current 20 mA)
-10.5 Vdc (max allowable current 20 mA)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 k)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 k)
4 to 20 mA, 0 to 20 mA (input impedance: 250 )
Voltage or current input must be selected by DIP switch S1 and
H3-09
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 k)
Use switch S4 on the control terminal board to select between
analog input or PTC input. If PTC is selected, set H3-06 = E.
0 V
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA