2.4
Network Wiring
The instrument is shipped with 2 meters (6 feet) of permanently
attached 3-wire shielded cable extending from the bottom of the
unit.
The open end of the cable should be terminated in a junction
box:
• white ..............marked D+ .......to D
• brown.............marked –..........to P–
• green..............marked P+ .......to P+
• cable shield.............................to S.
To interface with external control systems, use of a 3–wire shielded cable 3x1.0 mm2 / 17 AWG is
recommended.
Junction Box 2 nodes, standard
Satellite XT 4-20 mA Versions
Installation and Start-Up - Section 2
Junction Box Terminals
D
white
P-
brown
P+
green
S
shield
109,5mm
4-20 mA Output
0 V (common)
12 ... 24 VDC
Power
cable shield
2-5