Table of Contents

Advertisement

Quick Links

X4 Series
Operating Instructions and
Maintenance Manual

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell X4 Series

  • Page 1 X4 Series Operating Instructions and Maintenance Manual...
  • Page 2 Alternative language versions are available for download from the Honeywell Analytics website www.honeywellanalytics.com Alternatieve talen versies zijn electronisch beschikbaar via onze web pagina van Honeywell Analytics: www.honeywellanalytics.com Les versions alternatives de langue sont disponibles pour le téléchargement du website www.honeywellanalytics.com de Honeywell Analytics Las versions alternativas de la lengua están disponibles para la transferencia...
  • Page 3 For your safety, it is required to calibrate the detector periodically (See Section 4 Calibration). Honeywell Analytics can take no responsibility for use of its equipment if it is not used in accordance with the instructions stated in the relevant manual. If further details are required but not provided in this manual, contact Honeywell Analytics or their agent.
  • Page 4 No gas will be detected while in the set-up mode or the gas exposure status review mode. • The desktop USB memory card reader and data logging kit are not certified intrinsically safe and must not be used in potentially hazardous atmospheres. X4 Series...
  • Page 5 Contacting Honeywell Analytics Customer Business Centers Americas (Minimax4 series) Europe and ROW (ImpulseX4 series) 400 Sawgrass Corporate Parkway Wilstrasse 11-U11 Suite 100 Ch-8610 Uster Sunrise, Florida 33325 Switzerland Tel: +1 954 514 2700 Tel: +41 (0)1 943 4300 Toll free: +1 800 538 0363...
  • Page 6 Chaque jour, avant toute utilisation, tester la sensibilité sur une concentration connue de méthane équivalente à 25-50% LEL. La précision doit être comprise dans une plage de +/-20% de concentration réelle. a précision peut être corrigée en effectuant un étalonnage approprié du détecteur. X4 Series...
  • Page 7 Honeywell analytics charger (part number 2566-0484) when charging the sealed rechargeable battery pack (part number 2566-0482 for Minimax4 series and part number 2566-0462 for impulse X4 series). use of any other charger will void the intrinsic safety certification of the instrument.
  • Page 8 Warning use only the Honeywell analytics supplied ac adapter (part number 2566-0483) to connect to the cradle charger (part number 2566-0484). aVErtissEMEnt utiliser uniquement l’adaptateur à courant alternatif Honeywell analytics fourni (référence 2566-0483) pour connecter l’instrument au chargeur socle (référence 2566-0484).
  • Page 9: Table Of Contents

    4--. Span Gas Information ........6 4--. Span Gas Setting ........... 4--4. Gas Search and Countdown ...... 4--5. Span Calibration Result ........8 5. Set-Up Mode ..............29 5-1. Entering the Set-Up Mode ........30 5-2. Changing the Detector Set-Up .......31 5-3. Exiting the Set-Up Mode.........31 X4 Series...
  • Page 10 C-2. Accuracy Statement ..........47 C-3. Declaration ..............48 C--1. Declaration for the Minimax4 series ....48 C--. Declaration for the ImpulseX4 series .....49 Appendix D ................50 D-1. Specifications ............50 D-1-1. Specifications for the Minimax4 series ...50 D-1-. Specifications for the ImpulseX4 series ..51 X4 Series...
  • Page 11: Introduction

    1. Introduction The X4 series is an easy to use personal gas detector, designed for monitoring the atmosphere for potentially hazardous levels of flammables, oxygen, carbon monoxide, and hydrogen sulfide. It uses a front-mounted LCD display to show readings of the gases being measured and other useful information. A loud audible alarm and bright visual alarm are used to warn users when the concentrations of measured gases exceed the alarm set points.
  • Page 12: Basic Button Operation

    (for flammable and toxic) mode in a low light area, press the UP or DOWN button once. Zero Calibration Icon Span Calibration Icon Gas Label Icon Deficiency Alarm Icon Excess Alarm Icon X4 Series...
  • Page 13: Standard Accessories

    1-4. Standard Accessories The items listed below are included with the X4 series. For damaged or missing parts, contact Honeywell Analytics or their agent. Part No. Description 2566-0424 Calibration Certificate 2566-0422 Quick Start Guide 2566-0433 Alkaline Batteries (1.5V AA), Energizer E91 or EN91 ®...
  • Page 14: Clearing The Stel And Twa Values

    “Data Fu” message and the “Delete no” prompt will not be displayed). Press the UP or DOWN buttons to scroll to “no” or “YES” and press the ON/OFF button to select. X4 Series...
  • Page 15: Power-Up Self-Test

    2-2. Turning the Detector Off To turn off the detector, press and hold the ON/OFF button while in the measuring mode. A countdown will be displayed for 5 seconds, and then the detector will beep and turn off. X4 Series...
  • Page 16: Operation

    O deficiency) alarm set points • Display the STEL and TWA alarm set points (for CO & H S only). Level 1 Level 2 stEL *Examples shown for default settings of each gas for the Minimax4 series. X4 Series...
  • Page 17: Measuring Mode

    5 seconds. note If the Self-Test has failed, repeat the Self-Test. If a second failure occurs, contact Honeywell Analytics or their agent 3-2. Measuring Mode The detector may be used as either a “diffusion” or “sample-draw” type monitoring device. In normal operation, the detector is worn on the belt or held by hand. Once turned on, the detector monitors continuously.
  • Page 18: Flipping The Display

    15% of the applied gas concentration, a span calibration should be performed, under conditions of standard temperature (15°C to 5°C), humidity and pressure. Follow local regulations and/or your company’s policy on the frequency of bump testing. For more information on test gas, contact your local Honeywell Analytics representative. 3-4. Gas Alarms...
  • Page 19: Gas Alarms For The Minimax4 Series

    2 alarms are set to the same value, the level 2 alarm action overrides the level 1 alarm. The maximum value of the level 2 alarm in %Vol for flammable gas varies depending on the gas. (See Appendix B-2 Flammable Lower Explosive Limit.) X4 Series...
  • Page 20 When the reading returns to a normal level, the audible, visual and vibrating alarms will stop. If the measured reading exceeds the range of the sensor, the full-scale value will blink. See Section 5 Set-up Mode for more information on Latching/Non- Latching Alarms X4 Series...
  • Page 21: Gas Exposure Status Review

    Current Date Current date in MM DD - YY format (US) or DD MM - YY format (EU) Current Time Current time in HH:MM:SS format (24 hour format) * Examples shown for the status review for the Minimax4 series X4 Series...
  • Page 22: Confidence Flash/Beep

    Memory card readers can be purchased from Honeywell Analytics or from a local source of your choice. Card Readers must be able to read both MMC (MultiMediaCard) and SD (SecureDigital) cards.
  • Page 23 When the data Logging icon is either blinking or not displayed, it indicates that no data is being logged. To install or remove the memory card, see Section 6- Installing or Removing the Memory Card. X4 Series...
  • Page 24: Calibration

    The detector will initiate a ZERO calibration showing a blinking ZERO Calibration icon and a countdown from ‘00’ to ‘000’. Countdown • When the ZERO calibration has been completed successfully for all sensors, the Test Pass icon will blink for 5 seconds. X4 Series...
  • Page 25: Span Calibration (For Flammable And Toxic Sensors Only)

    Fail note If any sensor has failed, repeat the ZERO calibration ensuring that the detector is in fresh air. If a second failure occurs, contact Honeywell Analytics or their agent. Warning under proper calibration procedures, repetitive calibration failures could indicate that the sensor is either approaching its end of life, or it has been seriously contaminated, or both.
  • Page 26: 1. Pass Code Input

    If the user fails to input the correct pass code 3 times consecutively, the detector will return to measuring mode. notE For lost pass code, contact Honeywell Analytics or their agent. 4-3-2. Span Gas Information The SPAN gas information will be displayed.
  • Page 27: Span Gas Setting

    If no gas is detected within 30 seconds, the detector will give a single beep and a single flash, indicate an error “Err” for all gases on the LCD display, blink the Test Fail icon for 5 seconds, and then exit calibration mode. X4 Series...
  • Page 28 Repeat the SPAN calibration ensuring that the calibration gas used is of the correct concentration, there is sufficient gas in the cylinder and the flow rate is correct. If a second failure occurs, contact Honeywell Analytics or their agent. all Pass...
  • Page 29: Set-Up Mode

    Enables or disables the pass code protection and changes the current pass code as required. (Factory default pass code protection setting is “oFF”. The factory default pass code is “000”.) note To proceed, the detector prompts the user to enter the current valid pass code. X4 Series...
  • Page 30: Entering The Set-Up Mode

    If the Pass Code Protection feature has been activated, the detector prompts the user to enter the pass code. (See Section 4--1 Pass Code Input.) X4 Series...
  • Page 31: Changing The Detector Set-Up

    5-3. Exiting the Set-Up Mode In set-up mode, if no button is pressed within 0 seconds, or both the UP and DOWN buttons are pressed together and held for  seconds, the detector will revert back to the measuring mode. X4 Series...
  • Page 32: Maintenance

    Dispose of batteries according to local or national regulations. • Insert battery holder into the detector, turn the locking tab 90° clockwise, and return the locking tab to its original position. Lift Pull Turn 90º X4 Series...
  • Page 33: Installing Or Removing The Memory Card

    2566-0482 for Minimax4 series and part number 2566-0462 for impulse X4 series). use of any other charger will void the intrinsic safety certification of the instrument. use only the Honeywell analytics supplied aC adaptor (part number 2566-0483) to connect to the charger (part number 2566-0484).
  • Page 34: Replacing The Expired Sensor

    Clean the exterior of the detector with a clean damp cloth. • Clean the sensor grilles with a soft brush. 6-4. Replacing the Expired Sensor If the sensor reaches the end of its recommended life, contact Honeywell Analytics or their agent to arrange sensor replacement service. X4 Series...
  • Page 35: Optional Accessories

    (*) are not certified intrinsically safe and must not be used in potentially hazardous atmospheres. See Section 1-4 Standard Accessories for the part numbers of the standard (included) items. For inquiry see the Contacting Honeywell Analytics section on page 5. X4 Series...
  • Page 36: System Configuration Options

    ImpulseX-3-OFXH 2 gas Impulse X4 with O , Flammable sensors ImpulseX-2-OFXX 1 gas Impulse X4 with Flammable sensor ImpulseX-1-XFXX 1 gas Impulse X4 with O sensor ImpulseX-1-OXXX For inquiry see the Contacting Honeywell Analytics section on page 5. X4 Series...
  • Page 37: A-1. Calibration Mode Menu Structure 1/2

    (Exp / CO / H wait for 10 seconds < 3 Gas Calibration > Span Gas Search balance No Gas Found span gas search No gas for up to 30 seconds found Span Calibration 60 seconds countdown with span calibration icon blinking X4 Series...
  • Page 38: A-2. Calibration Mode Menu Structure 2/2

    < 1 Gas Calibration > Span Gas Search balance No Gas Detected span gas search No gas for up to 30 seconds detected Span Calibration 60 seconds countdown with span calibration icon blinking Span Cal. Span Cal. Success Fail Span Cal. Fail X4 Series...
  • Page 39: A-3. Set-Up Mode Menu Structure 1/4

    --------------------- < ON/OFF > < ON/OFF > to save the value to save H S value scroll to the next gas (CO / H < UP > or < DOWN > X4 Series...
  • Page 40: A-4. Set-Up Mode Menu Structure 2/4

    Year data to save and scroll to to save and scroll to the next setting the next setting (US / MM / DD / YY) (EU / DD / MM / YY) < UP > or < DOWN > X4 Series...
  • Page 41: A-5. Set-Up Mode Menu Structure 3/4

    User ID No 001 ~ 999 Setting ---------------------- < ON/OFF > < UP > to activate the function to increase < ON/OFF > < DOWN > to save the new number to decrease < UP > or < DOWN > X4 Series...
  • Page 42: A-6. Set-Up Mode Menu Structure 4/4

    On/Off --------------------- to activate the function < ON/OFF > to save the status < ON/OFF > scroll to the next gas to save H S status / Exp / CO / < UP > or < DOWN > X4 Series...
  • Page 43: B-1. Sensor Cross-Sensitivity

    Hydrogen (100 ppm) Hydrogen Sulfide (10 ppm) Iso-Propanol (200 ppm) Nitric Oxide (25 ppm) Nitrogen Dioxide (3 ppm) Sulfur Dioxide (2 ppm) B-1-2. O Cross-Sensitivity Gas Applied Response (% Vol) Hydrogen (100% vol) Methane (100% vol) Nitrogen Dioxide (5 ppm) X4 Series...
  • Page 44: B-1-. Flammable Cross-Sensitivity

    When the detector is exposed to such shocks, a check should be performed on the sensors to verify accuracy (and a calibration performed if necessary). X4 Series...
  • Page 45: B-2. Flammable Lower Explosive Limit

    For measuring other gases listed in the table, the detector should be calibrated with the target gas at relevant concentration and the proper Correction Factor needs to be set depending on the standard to be used. X4 Series...
  • Page 46: C-1. Warranty

    Appendix C C-1. Warranty All products are designed and manufactured to the latest internationally recognized standards by Honeywell Analytics under a Quality Management system that is certified to ISO 9001:000. Device Warranty Terms 24 months from date of switch on / installation provided this takes place prior to the ‘Activate Before’...
  • Page 47: C-2. Accuracy Statement

    To achieve optimal accuracy, the detector should be periodically supplied with a known concentration test gas, and if the readings are outside of 15% of the applied gas concentration, a span calibration should be performed, under conditions of standard temperature (15°C to 5°C), humidity and pressure. X4 Series...
  • Page 48: C-3. Declaration

    C-3. Declaration C-3-1. Declaration for the Minimax4 series X4 Series...
  • Page 49: C--. Declaration For The Impulsex4 Series

    C-3-2. Declaration for the ImpulseX4 series X4 Series...
  • Page 50: D-1. Specifications

    Dimensions 124 mm (H) x 76 mm (W) x 36 mm (D) (4.9 in x 3.0 in x 1.4 in) Weight 210 g w/o batteries, 258 g w/batteries (7.4 oz w/o batteries, 9.1 oz w/batteries) Warranty 2 years X4 Series...
  • Page 51: D-1-. Specifications For The Impulsex4 Series

    124 mm (H) x 76 mm (W) x 36 mm (D) (4.9 in x 3.0 in x 1.4 in) Weight 210 g w/o batteries, 258 g w/batteries (7.4 oz w/o batteries, 9.1 oz w/batteries) Warranty 2 years Energizer is a trademark of the Eveready Battery Company, Inc. X4 Series...
  • Page 52 NETHERLANDS, Baam Customer business center Customer business center Americas Canada Honeywell Analytics Honeywell Analytics - Vulcain 400 Sawgrass Corporate Pkwy 4005 Matte Boulevard Suite 100 Unit G Sunrise, FL 5 Brossard, QC J4Y P4 Tel: +1 954 514 00...

Table of Contents