Wiring And Terminations - SecEng SED-64 Installation & User Manual

3g alarm backup rev 4 (software 021)
Table of Contents

Advertisement

1.3
Terminal Connections
Terminal
POWER
Earth
16 vac
16 vac
BATT +
BATT -
FAULT RELAY
NC
C
N0
ZONE INPUTS
C
4
3
C
2
1
PSTN
CON 1

Wiring and Terminations

Description
Connect to mains earth via plug pack
Note: remove solder tinning on earth wire, if provided, before connecting.
AC input 16v AC plug pack ( As supplied with unit only )
AC input 16v AC plug pack ( As supplied with unit only )
12v DC battery input Positive
12v DC battery input Negative
normally closed contact
common contact
normally open contact
Warning: fault relay is at TNV-3 and is rated 0.5 A at 125 vac
(24hr Multibreak) 10k E.O.L. ( MUST BE INSTALLED )
Common for Zones Inputs ( negative float )
10k end of line resistor required to common
10k end of line resistor required to common
Common for Zone Inputs ( negative float )
10k end of line resistor required to common
10k end of line resistor required to common
To Mode 3 T-Socket ( to panel and phone line )
Used for programming via telephone handset and for audio across GSM