4.3
GPRS Testing MODE 1
BASIC GPRS COMMS
1/ If the OH light is flashing every 3 seconds then rapidly every 40 seconds
you are polling on GPRS.
Call Suretek on 1300 65 44 33 to confirm the SED-64 is polling via GPRS.
TESTING ALARMS MODE 1
Trigger a zone on the SED-64 and check that the OH light starts to flash for
approximately 5 seconds, this confirms the SED-64 has sent zone alarm via
GPRS.
If you now disconnect the T piece socket from the phone line, it should after
30 seconds send a line fail thru via GPRS.
IF you now trigger the customers alarm panel it should send an alarm thru
via the normal Contact Id receiver via GSM and not via GPRS.
GPRS Testing MODE 2
BASIC GPRS COMMS
1/ If the OH light is flashing every 3 seconds, then rapidly every 40
seconds, you are Polling on GPRS.
Call Suretek on 1300 65 44 33 to confirm the SED-64 is polling via GPRS.
TESTING ALARMS mode 2
With GPRS MODE 2 all alarms are converted to data from Contact ID
With the T socket disconnected from the phone line, now trigger the
customers alarm panel. The OH light will light up and the panel will now
dial through the SED-64. If you plug a butt into CON1 you will be able to
hear the Contact ID conversion as the SED-64 is acting as a Contact ID
receiver.
Once converted to GPRS DATA the OH light will flash to indicate it is
sending the captured alarms via GPRS.
Check with your control room as the alarms should have gone through via
GPRS.