Relevant Failure Modes; Fault Exclusions; Operation Delays - ABB ACS880-07 User Manual

Emergency stop, stop category 0 (option +q951)
Hide thumbs Also See for ACS880-07:
Table of Contents

Advertisement

30 Option description and instructions
Diagram 4: ACS880-17/37 drives, frames nxR8i + nxR8i
E-stop
button
Auxiliary
safety
relay

Relevant failure modes

The main contactor does not open when requested. (All contactor failures are
considered dangerous.)
Internal failures of safety relays and the emergency stop button. These failures are
included in the PFH value of the function.

Fault exclusions

Fault exclusions (not considered in the calculations):
any short and open circuits in the cables of the safety circuit
any short and open circuits in the cabinet terminal blocks of the safety circuits.

Operation delays

Emergency stop total delay: less than 250 ms
Auxiliary
E-stop
safety
safety
relay
relay
Main
contactor
or
circuit
breaker
Charging
contactor

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs880-17Acs880-37Acs580-07Acq580-07Ach580-07

Table of Contents