20 Option description and instructions
Use of the safety function
Activating
1. Push the emergency stop button [S61]. The emergency stop activates and the button
locks in "ON" (open) position.
Resetting
1. Turn the emergency stop button [S61] until it releases.
2. Push the emergency stop reset button [S62] on the cabinet door. The indication lamp
[P62] of the reset button [S62] goes out, the emergency stop deactivates.
3. Reset the drive if necessary.
4. If necessary, close the main contactor with the operating switch (see the hardware and
firmware manuals).
The main contactor/breaker closes and the drive is powered up.
5. Make sure that the drive has received the start signal (depends on the configuration,
see the firmware manual).
6. You can now restart the drive.
Note: You have to reset the emergency stop circuit with the reset button [S62] also after
you have powered up the drive.
Emergency stop indications
When the emergency stop is on:
•
the drive control program has the warning Safe torque off active,
•
the emergency stop reset button [S62] on cabinet door is illuminated (indication lamp
[P62]).
Fault tracing
This table describes the status LEDs of the emergency stop safety relay [A61].
LED
LED is lit and steady
Netz
Power supply is connected.
K1
Relay K1 is energized.
K2
Relay K2 is energized.
To reset the emergency stop safety relay [A61] after fault situations, switch off the external
power supply of the safety relay.
For more fault tracing possibilities, see the hardware and firmware manuals of the drive.