Acs880-17/37 Drives, Frames Nxr8I + Nxr8I - ABB ACS880-07 User Manual

Emergency stop, stop category 0 (option +q951)
Hide thumbs Also See for ACS880-07:
Table of Contents

Advertisement

Step
Operation
3.
The emergency stop indication lamp [P62] of emergency stop reset button [S62] switches on.
4.
The motor coasts to zero speed and remains at zero speed while the emergency stop is active.
5.
Normal operation resumes after the user:
• releases the emergency stop button [S61] to normal (up) position
• resets the emergency stop circuit with the emergency stop reset button [S62]
• resets the drive (if the STO indication parameter 31.22 has been set so that a fault is generated).
If the drive is used in remote control mode, see firmware manual for more information.

ACS880-17/37 drives, frames nxR8i + nxR8i

-S61
L
L
-K62.1
-K62.3
-Q1/2
-Q4
1)
Reset circuit
A41
Control board (inverter unit)
A51
Control board (supply unit)
A61
Emergency stop safety relay
K62.1 Auxiliary safety relay
K62.2 Auxiliary relay
K62.3 Auxiliary safety relay
X969
STO terminal block
Initial status: The drive is in operation and the motor is running.
Step
Operation
1.
The user activates emergency stop by pushing the emergency stop button [S61].
Control relays
-T22
24 V
1)
-Q1/2
-K62.1
-Q4
-K62.3
-S62
-A61
-K62.1
-K62.2
-K62.3
Option description and instructions 15
Drive control boards
-A51
-K62.2
-A41
-K62.2
OUT
SGND
IN1
IN2
-P62
-X969
S61
Emergency stop button
S62
Emergency stop reset button
P62
Emergency stop indication lamp
Q1/2
Main contactor
Q4
Charging contactor
T1
Drive module
T22
24 V power supply
Main circuit
24 V
DIIL
-Q1/2
-T1
XSTO
M
3~
1-2
3-4
-Q4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs880-17Acs880-37Acs580-07Acq580-07Ach580-07

Table of Contents