10.In the tree view, select the folder System > Shared Folders > Shares.
11.Look for the archive path in the list in the "Shared Path" column.
4.1.3

How to Prepare the Software Update with Central Archiving

Requirement
Before you run the software update, perform these steps directly on the archive server (Central
Archive Server (CAS), or StoragePlus Server).
Lock Archiving
To prevent new data from being entered in the central archive server, the archive server can
be locked for archiving. The data is then saved on the OS server.
1. In the Windows Control Panel, double-click the "Administrative Tools" icon and then
2. In the tree view, select the folder System > Shared Folders > Shares.
3. Select the archive path from the list.
4. Select the menu command Action > Clear Share.
5. Click "Yes".
Note
The CAS downtime must not exceed the shortest circular archive time of the OS servers.
4.1.4
How to Detach Attached Archive Segments on the Central Archive Server
Requirements
● Before you run the software update, perform these steps directly on the archive server
● You are authorized to access the Windows user interface on the CAS.
Software update without utilization of new functions
Service Manual, 03/2012, A5E02779792-02
The archive share name for the OS archives is displayed in the "Shared Folders" column
in this line.
"Computer Management".
The "Shared Folders" dialog box is displayed.
(Central Archive Server (CAS), or StoragePlus Server).
Preparing for the software update
4.1 Adapt the central archive server