Mixed Operation Of Faceplates From Different Versions Of Pcs 7 - Siemens SIMATIC PCS 7 Service Manual

Process control system software update without utilization of new functions
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Adaptations in the PCS 7 project on the ES
6.4 Adaptation of OS-relevant settings
6.4.4

Mixed Operation of Faceplates from Different Versions of PCS 7

Definition of Mixed Operation
Mixed operation is the visualization of AS blocks from different PCS 7 versions on one OS
client.
Compatibility of PCS 7 V8.0 faceplates
Note
You can use the PCS 7 V8.0 faceplates to operate and monitor the AS blocks of the following
PCS 7 versions:
● PCS 7 V7.1 SP3
● PCS 7 V8.0
Rules
NOTICE
Mixed operation is only permitted on OS clients.
● AS blocks of different PCS 7 versions can be visualized on an OS client if the server data
● It is only ever possible to load the AS blocks of one PCS 7 version to an AS and an OS
6.4.5
How to Update the Picture Objects
Introduction
If you have manually inserted and interconnected picture objects from a picture template into
a process picture, you must manually update these picture objects.
When you update picture objects, the block icons of the previous PCS 7 version are replaced
with the latest PCS 7 block icons.
You have to use the corresponding picture template that you used for configuration to update
the picture objects.
Recommendation: Perform the update one by one with each picture template of the library
used.
46
of several OS servers is loaded to the OS client with AS blocks of different PCS 7 versions.
server.
Software update without utilization of new functions
Service Manual, 03/2012, A5E02779792-02