Set Values For Monitoring The Bearing Temperature (Optional) - Siemens SIMOTICS M-1PH818 Operating And Installation Instructions

Main motors
Table of Contents

Advertisement

7.6

Set values for monitoring the bearing temperature (optional)

Prior to commissioning
If the machine is equipped with bearing thermometers, set the temperature value for
disconnection on the monitoring equipment before the first machine run.
Table 7-2
Set value
Alarm
Shutting down
Normal operation
Measure the normal operating temperature of the bearings T
°C. Set the values for shutdown and warning corresponding to the operating temperature T
Table 7-3
Set value
Alarm
Shutting down
SIMOTICS M-1PH8 1PH818., 1PH822., 1PH828.
Operating Instructions 10/2017
7.6 Set values for monitoring the bearing temperature (optional)
Set values for monitoring the bearing temperatures before commissioning
Set values for monitoring the bearing temperatures
Commissioning
Temperature
115 °C
120 °C
at the installation location in
op
Temperature
T
+ 5 K ≤ 115 °C
operation
T
+ 10 K ≤ 120 °C
operation
.
op
93

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotics m-1ph828Simotics m-1ph822

Table of Contents