Setting The Automatic Regreasing System; Setpoint Values For Monitoring The Bearing Temperature; Table 7-1 Set Values For Monitoring The Bearing Temperatures Before Commissioning; Table 7-2 Set Values For Monitoring The Bearing Temperatures - Siemens SIMOTICS FD 1LM1 Operating Instructions Manual

Low-voltage motor
Table of Contents

Advertisement

See also
Regreasing intervals and types of grease for operating roller bearings (Page 117)
Stoppages (Page 107)
Transport (Page 34)
7.5

Setting the automatic regreasing system

The relubrication is performed depending on the external voltage present at the regreasing
system.
● Prior to commissioning, set the time interval and the relubrication quantity at the automatic
● Observe the operating instructions for the regreasing system for its operation and the
See also
Interlock circuit for the automatic regreasing system (option) (Page 31)
7.6

Setpoint values for monitoring the bearing temperature

Prior to commissioning
If the machine is equipped with bearing thermometers, set the temperature value for
disconnection on the monitoring equipment before the first machine run.
Table 7-1
Set value
Alarm
Shutting down
Normal operation
Determine the maximum operating temperature of the bearings T
temperature, bearing load and influences of the plant on the motor in °C. Set the values for
shutdown and warning corresponding to the operating temperature T
Table 7-2
Set value
Alarm
Shutting down
SIMOTICS FD 1LM1
Operating Instructions 01/2019
regreasing system.
replacement of the grease cartridges.
Set values for monitoring the bearing temperatures before commissioning
Set values for monitoring the bearing temperatures
7.5 Setting the automatic regreasing system
Temperature
115 °C
120 °C
taking into account the
operation
.
op
Temperature
T
+ 5 K ≤ 115 °C
operation
T
+ 10 K ≤ 120 °C
operation
Start-up
95