Further Documents; Setpoint Values For Monitoring The Bearing Temperature; Switching On - Siemens SIMOTICS XP Eagle Line 1MB1.33 Operating Instructions Manual

Low-voltage motors, shaft heights 71...315
Table of Contents

Advertisement

7.1.4

Further documents

Note
Further documents
Observe all of the other documents provided with this machine.
7.2

Setpoint values for monitoring the bearing temperature

Prior to commissioning
If the machine is equipped with bearing thermometers, set the temperature value for
disconnection on the monitoring equipment before the first machine run.
Table 7- 1
Set value
Alarm
Shutting down
Normal operation
Determine the maximum operating temperature of the bearings T
the temperature, bearing load and influences of the plant on the motor in °C. Set the values
for shutdown and warning corresponding to the operating temperature T
Table 7- 2
Set value
Alarm
Shutting down
7.3

Switching on

Measures for start-up
After installation or inspections, the following measures are recommended for normal start-
up of the machines:
• Start the machine without a load. To do this, close the circuit breaker and do not switch
off prematurely. Switching the machine off again while it is starting and still running at
slow speed should only be done to the extent necessary, for example for checking the
1MB1.33 Eagle Line shaft heights 71 ... 315
Operating Instructions, 08/2023, A5E52990459A
7.2 Setpoint values for monitoring the bearing temperature
Set values for monitoring the bearing temperatures before commissioning
Set values for monitoring the bearing temperatures
Commissioning
Temperature
115 °C
120 °C
taking into account
operation
.
op
Temperature
T
+ 5 K ≤ 115 °C
operation
T
+ 10 K ≤ 120 °C
operation
107

Advertisement

Table of Contents
loading

Table of Contents