Figure 6-1 Terminal Lug For The Grounding Conductor For A Force-Ventilated Motor; ① For The Grounding Conductor For A Force-Ventilated Motor; Preparation - Siemens SIMOTICS M-1PH818 Operating And Installation Instructions

Main motors
Table of Contents

Advertisement

Electrical connection

6.1 Preparation

6.1
Preparation
6.1.1
Selecting cables
Take the following criteria into account when selecting the connecting cables:
● Rated current
● Rated voltage
● If required, service factor
● System-dependent conditions, such as ambient temperature, routing type, cable cross-
● Configuration notes
● Requirements according to IEC/EN 60204‑1
6.1.2
Connect up the ground conductor
The grounding conductor of the motor must be in full conformance with the installation
regulations, e.g. in accordance with IEC/EN 60204-1.
● Connect the ground conductor to the end shield of the motor. There is a fixing lug
● When making connections, ensure the following:
Figure 6-1
68
section as defined by required length of cable, etc.
the ground conductor at the designated connection point.
– The fixing lug
is suitable for grounding high-frequency currents using HF ribbon cable
with appropriately formed conductor ends.
– the connecting surface is bare and protected against corrosion using a suitable
substance, e.g. acid-free Vaseline
– the flat and spring washers are located under the bolt head.
Terminal lug
for the grounding conductor for a force-ventilated motor
SIMOTICS M-1PH8 1PH818., 1PH822., 1PH828.
Operating Instructions 10/2017