ABB CDD Product Manual page 48

Concentrator data device
Table of Contents

Advertisement

Display code
Cause
LED status
Message
W003
This alarm is generated when
Blinking
one or more grid parameters lie
green
outside the permitted range set
Grid Fail
by the country of installation's
grid standard. The error code will
W004
be followed by a suffix in brack-
Blinking
ets indicating the grid parameter
green
out of range:
VAC OV
(UV) Grid voltage below the set
lower limit
W005
(OV) Grid voltage above the set
Blinking
upper limit
green
(UF) Grid frequency below the
VAC UV
set lower limit
(OF) Grid frequency above the
set upper limit
W011
Internal fault of the booster circuit
Solid red
inverter
Vbulk UV
W032
MICRO is limiting AC power due
Blinking
to an external condition; not an
green
error but a certain working condi-
Pgrid limita-
tion
tion
W033
MICRO is limiting AC power due
Blinking
standard frequency regulation.
green
Pgrid Fgrid
limitation
W034
MICRO is limiting AC power due
Blinking
to a standard voltage regulation.
green
Pgrid VAC
high limitation
W035
Fgrid problem
Blinking
green
Solution
If the error is generated only on one of
the installation MICRO inverters, this
may be due to an inverter fault.
If the alarm is generated at multiple
inverters in the installation, check the
grid voltage for instabilities in any of
the 4 parameters monitored by the
inverter. If anomalous values are de-
tected, verify the sizing of the AC line
conductors. In case of correct sizing,
please contact your grid operator to
address the problem.
Contact customer service.
If problem persists check grid connec-
tion condition.
If problem persists check grid frequen-
cy condition.
If problem persists check grid voltage
condition.
(UF) grid frequency below the set
lower limit
(OF) grid frequency above the upper
limit
- 48 -
7 - Appendix