YASKAWA V1000 Installation Manual page 39

Compact vector control drive nema type 4x/ip66, cimr-v**a series, 200 / 400 v class, singe / three-phase input: 0.1 / 0.2 to 18.5 / 3 kw
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

Cable Glands for Asia
Yaskawa recommends the following SC cable glands but is not limited to SEIWA
ELECTRIC MFG Co., Ltd. for the V1000 NEMA Type 4X/IP66 drive. The SEIWA cable
gland is not readily available outside of Asia.
Table 20 Cable Glands for Drive Main Circuit Wiring
Voltage
Model No.
Class
CIMR-V
BA0001G
BA0002G
Single-
BA0003G
Phase
200 V
BA0006G
Class
BA0010G
BA0012G
2A0001G
2A0002G
2A0004G
2A0006G
2A0008G
2A0010G
Three-
Phase
2A0012G
200 V
Class
2A0018G
2A0020G
2A0030G
2A0040G
2A0056G
2A0069G
YASKAWA ELECTRIC TOBP C710606 35D YASKAWA AC Drive - V1000 NEMA Type 4X/IP66 Installation Manual
Conduit
Hole Diameter
mm
Input
Output
Option
Holes
Holes
Holes
22
22
22
28
28
28
22
22
22
28
28
28
44
44
22
50
50
22
8 Cable Gland Selection
Cable Gland (Seiwa)
Appropriate
Wiring
Product
Diameter
Number
mm
10.5 to 12.5
SCL-14A
10.6 to 12
SC-4A
12.1 to 14
SC-4B
14.1 to 16
SC-4C
10.5 to 12.5
SCL-14A
10.6 to 12
SC-4A
10.6 to 12
SC-4A
12.1 to 14
SC-4B
14.1 to 16
SC-4C
14.1 to 16
SC-4C
20.1 to 22
SC-6M
22.1 to 24.5
SC-6A
30 to 32
SCL-38A
Tightening Torque
Nm
Body,
Body, Cap
Locknut
2.5 to 2.9
2.9 to 3.4
2.0 to 2.5
2.9 to 3.4
2.5 to 2.9
2.9 to 3.4
2.0 to 2.5
2.9 to 3.4
4.9 to 5.3
5.8 to 6.3
3.4 to 3.9
4.9 to 5.3
39