Installation Standards - YASKAWA MP2600iec Hardware Manual

Hide thumbs Also See for MP2600iec:
Table of Contents

Advertisement

3.2 Installation Standards

3.2 Installation Standards
The servo amplifier must be installed in a fully enclosed metal control panel. Observe the standards
for mounting servo amplifiers in control panels, including those for the mounting servo amplifiers side
by side in one control panel as shown in the following illustration.
• Servo Amplifier Mounting Orientation
Mount the servo amplifier vertically to the wall, with the front panel (the side with the panel operator
display) facing out.
• Cooling
Refer to the following diagram and leave sufficient space for cooling by fans and natural convection.
• Mounting Servo Amplifiers Side by Side in a Control Panel
30 mm or more
Leave sufficient space on each side and at the top and the bottom of each servo amplifier. The
width on each side varies in accordance with the models of the servo amplifiers used.
Servo Amplifier Model for
Sigma-5 (SGDV- ) or Sigma-7 (SGD7S- )
R70F, R90F, 2R1F, R70A, R90A, 1R6A, 2R8A
2R8F, 3R8A, 5R5A, 7R6A
120A, 180A, 200A, 330A, 470A, 550A, 590A, 780A,
1R9D, 3R5D, 5R4D, 8R4D, 120D, 170D, 210D, 260D,
280D, 370D
Also install cooling fans above the servo amplifiers to disperse local pockets of warmer air around
the servo amplifiers.
• Inside the Control Panel
The conditions inside the control panel should be the same as the environmental conditions of
the servo amplifier. Refer to the environmental conditions in 2.1 General Specifications
• During Operation
Do not touch the connectors or IO cables during operation if the panel door is open.
10
Fan
Width varies with
servo amplifier model
.
.
Fan
40 mm or more
40 mm or more
Side
Left
1 mm or more
1 mm or more 10 mm or more
10 mm or more
Top and bottom
Right
40 mm or more

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents