Statistical information
This function is only active when 'Trigger
band' ≠ 0.
'Trigger edge' = "Band entry"
w, x, y, e
Top band limit =
Trigger value + ½ trigger band
Trigger value
Bottom band limit =
Trigger value – ½ trigger band
Trigger band
The conditions for starting a trigger event
are met when the value exceeds the lower
limit ('Trigger value' – ½ 'Trigger band') or
falls below the upper limit ('Trigger value' +
½ 'Trigger band').
This function is only active when 'Trigger
band' ≠ 0.
Note
The bottom band limit assumes the value
0.0 % or 0.0
at the lowest. The top band
1
/
s
limit assumes the value 100.0 % or 100.0
at the most.
Diagnosis > Statistical information > Data
logger
1.
− Selection: Trigger
2. − Trigger status: Start trigger via set point,
valve position, drive signal or set point
deviation
34
− Trigger value:
0.0 to 100.0 %, [99.0 %] (set point, valve
position, set point deviation)
0.0 to 10000.0
− Trigger band:
0.0 to 100.0 %, [99.0 %] (set point, valve
position, set point deviation)
0.0 to 10000.0 
− Pre-trigger time:
0.0 s to 100 x 'Scan rate', [0.0 s]
− Trigger edge: [Low signal/falling edge/
bottom band exit], High signal/rising edge/
top band exit, Band exit, Band entry
3. − Scan rate: 0.2 to 3600.0 s, [1.0 s]
4. − Start data logger
Types 3730-4/-5: [Bottom band exit], Top
1)
band exit, Band exit, Band entry
4.2.2.3 Triggered by internal sole-
noid valve/forced venting
3730-2 3730-3 3731-3 3730-4 3730-5 3731-5
Function available in firmware 1.5x and lower
1)
Triggering by the internal solenoid valve/
forced venting is only active when an inter-
1
/
s
nal solenoid valve/forced venting is installed
in the positioner. See 'Internal solenoid
valve/forced venting' reading (Code 45).
The measured values are included in the trig-
gered data logging when the solenoid valve
is triggered or the forced venting is activat-
ed.
Diagnostics > Data logger
1.
− Selection: Trigger
, [99.0
] (drive signal)
1
/
1
/
s
s
, [99.0 
] (drive signal)
1
/
1
/
s
s
1)
EB 8389 EN
1)

Hide quick links:

Advertisement