Code
Parameter – Readings/
No.
values [default setting]
Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
E
Cancellation conditions of the partial stroke test (PST)
E0 Activation x control
[No]
1), 2), 3)
[YES]
4), 5)
49* E1 x control value
–10.0 to 110.0 % of
total travel, [0.0 %]
2), 3)
[85.0 %]
4), 5)
E2 Unassigned
E3 Unassigned
E4 Unassigned
E5 Activation PST
tolerance band control
[No], YES
E6 PST tolerance band
0.1 to 100.0 %,
[5.0 %]
E7 Max. test duration,
user-defined
30 to 25000 s,
[30 s]
1), 4), 5), 6)
[90 s]
 2), 3)
F
Partial stroke test (PST) information · Read only
F0 No test available
F1 Test OK
F2 x cancellation
F3 y cancellation
F4 Tolerance band
exceeded
EB 8389 EN
Description
Activates or deactivates x control.
The test is canceled when the valve position
– falls below the adjusted value (step end < step start)
– exceeds the adjusted value (step end > step start)
1),
Activates or deactivates PST tolerance band monitoring.
The test is automatically canceled as soon as the Step end (Code 49
- d3) exceeds this percentage.
Maximum time within which a test can be completed before the test
is canceled automatically.
No test available or test canceled manually.
The test was canceled by x cancellation function.
The test was canceled by y cancellation function.
The test was canceled. The x-values are outside the tolerance band.
Type 3730-2
1)
Type 3730-3
2)
Type 3731-3
3)
Type 3730-4
4)
Appendix
Type 3730-5
5)
Type 3731-5
6)
113