Appendix
Code
Parameter – Readings/
No.
values [default setting]
Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
49* d3 Step stop
0.0 to 100.0 %,
[90.0 %]
1), 2), 3)
[95 %]
4), 5)
d4 Activation of ramp
function
[No]
1), 2), 3), 5)
[YES]
4)
d5 Ramp time (rising)
0 to 9999 s,
[15 s]
1), 2)
[45 s]
, [60 s]
4), 5)
d6 Ramp time (falling)
0 to 9999 s,
[15 s]
1), 2)
[45 s]
, [600 s]
4), 5)
d7 Settling time before test
start
1.0 to 240.0 s,
[10.0 s]
1), 2)
[2 s]
, [1 s]
4), 5)
d8 Delay time after step
1.0 to 240.0 s
2.0 to 100.0 s
0.1 to 240.0 s
[2.0 s]
d9 Scan rate
0.2 to 250.0 s,
[0.2 s]
1), 2), 4), 5)
[0.8 s]
3)
112
Description
Stop value for step response
Activates or deactivates ramp function.
Ramp time for 0 to 100 % travel (rising) of ramp function
Initialization provides a sensible value that is not to be undercut, if
possible.
3)
Ramp time for 100 to 0 % travel (falling) of ramp function
Initialization provides a sensible value that is not to be undercut, if
possible.
3)
Waiting time before test is started to ensure that value for step start
can be reached safely.
3)
Waiting time between first step change and start of second step
change
,
1), 2), 3)
,
4)
,
5)
Scan rate of step response measurement
,
EB 8389 EN