3 Types of installation

3.1 Stand-alone installations

A stand-alone installation is a system disconnected from the public grid that provides AC. energy to a set of
loads.
Installation components:
Photovoltaic panels.
Battery bank.
ISS 1Play inverter.
Support diesel genset (optional) that is connected in the case of an energy deficit.
Manual bypass switch (optional). In the event of an ISS 1Play fault or maintenance, this allows for the
loads to be powered from the diesel genset. It is formed by 2 independent interlocking manual
switches that connect alternately.
To monitor this installation, an additional kit for Ethernet or Wi-Fi communications is required.
Although the INGECON SUN STORAGE 1Play provides an extra current during load connection transients
such as motors, INGETEAM recommends the use of frequency drives with this type of load to avoid transient
voltage drops (2-3 seconds) during their connection.
Technical notes:
The power of the loads must under no circumstances be above the rated power of the ISS 1Play.
The battery capacity must be at least C10
Technical Guide
5x P
Figure 7: Stand-alone single-phase installation
15/01/2018
/U
to ensure stable operation of the system.
PV
batt
INGECON SUN STORAGE 1Play
6/16