Certificate
Type
Intrinsically Safe
Gas
Ex ia IIC T5/T6 per drawing GE42990
Natural Gas Approved
Flameproof
DVC60x0
Gas
DVC60x0S
Ex d IIC T5/T6
(x = 1,2,3)
Natural Gas Approved
Type n
Gas
Ex nC IIC T5/T6
Natural Gas Approved
Intrinsically Safe
Gas
Ex ia IIC T5/T6 per drawing GE42990
Natural Gas Approved
Flameproof
IECEx
Gas
DVC6005
Ex d IIC T5/T6
Natural Gas Approved
Type n
Gas
Ex nC IIC T5/T6
Natural Gas Approved
Intrinsically Safe
Gas
Ex ia IIC T4/T5/T6 per drawing GE42990
DVC60x5
Flameproof
(x = 1,2,3)
Gas
Ex d IIC T4/T5/T6
Type n
Gas
Ex nA IIC T4/T5/T6
September 2013
Introduction and Specifications
Table 1-7. Hazardous Area Classifications—IECEx
Certification Obtained
Ui = 30 VDC
Ii = 226 mA
Ci = 5 nF
Li = 0.55 mH
Pi = 1.4 W
Ui = 30 VDC
Ii = 226 mA
Ci = 5 nF
Li = 0.55 mH
Pi = 1.4 W
Ui = 30 VDC
Ii = 100 mA
Ci = 0 uF
Li = 0 mH
Pi = 160 mW
Entity Rating
Temperature Code
T5(Tamb ≤ 80_C)
T6(Tamb ≤ 75_C)
T5(Tamb ≤ 80_C)
− − −
T6(Tamb ≤ 75_C)
T5(Tamb ≤ 80_C)
− − −
T6(Tamb ≤ 75_C)
Uo = 9.6 VDC
Io = 3.5 mA
T5(Tamb ≤ 80_C)
Ca = 3.6 uF
T6(Tamb ≤ 75_C)
La = 100 mH
Po = 8.4 mW
T5(Tamb ≤ 80_C)
− − −
T6(Tamb ≤ 75_C)
T5(Tamb ≤ 80_C)
− − −
T6(Tamb ≤ 75_C)
T4(Tamb ≤ 125_C)
T5(Tamb ≤ 95_C)
T6(Tamb ≤ 80_C)
T4(Tamb ≤ 125_C)
T5(Tamb ≤ 95_C)
− − −
T6(Tamb ≤ 80_C)
T4(Tamb ≤ 125_C)
− − −
T5(Tamb ≤ 95_C)
T6(Tamb ≤ 80_C)
Enclosure
Rating
IP66
Single Seal Device
1
IP66
Single Seal Device
IP66
Single Seal Device
IP66
Single Seal Device
IP66
Single Seal Device
IP66
Single Seal Device
IP66
IP66
IP66
1-11