Certification
Type
Body
IS Intrinsically Safe
Class I,II,III Division 1 GP A,B,C,D,
E,F,G per drawing GE42819
Natural Gas Approved
XP Explosion-proof
DVC60x0
Class I Division 1 GP B,C,D
DVC60x0S
NI Non-incendive
(x = 1,2,3)
Class I Division 2 GP A,B,C,D
DIP Dust Ignition-proof
Class II, III Division 1 GP E,F,G
S Suitable for Use
Class II, III Division 2 GP F,G
Natural Gas Approved
IS Intrinsically Safe
Class I,II,III Division 1 GP A,B,C,D,E,
F,G per drawing GE42819
Natural Gas Approved
XP Explosion-proof
FM
Class I Division 1 GP B,C,D
DVC6005
NI Non-incendive
Class I Division 2 GP A,B,C,D
DIP Dust Ignition-proof
Class II, III Division 1 GP E,F,G
S Suitable for Use
Class II, III Division 2 GP F,G
Natural Gas Approved
IS Intrinsically Safe
Class I,II,III Division 1 GP A,B,C,D,
E,F,G per drawing GE42819
XP Explosion-proof
DVC60x5
Class I Division 1 GP A,B,C,D
(x = 1,2,3)
NI Non-incendive
Class I Division 2 GP A,B,C,D
DIP Dust Ignition-proof
Class II, III Division 1 GP E,F,G
S Suitable for Use
Class II, III Division 2 GP F,G
September 2013
Introduction and Specifications
Table 1-5. Hazardous Area Classifications—FM (United States)
Certification Obtained
Vmax = 30 VDC
Imax = 226 mA
Ci = 5 nF
Li = 0.55 mH
Pi = 1.4 W
Vmax = 30 VDC
Imax = 226 mA
Ci = 5 nF
Li = 0.55 mH
Pi = 1.4 W
Vmax = 30 VDC
Imax = 100 mA
Ci = 0 uF
Li = 0 mH
Pi = 160 mW
Entity Rating
Temperature Code
T5(Tamb ≤ 80_C)
T6(Tamb ≤ 75_C)
T5(Tamb ≤ 80_C)
− − −
T6(Tamb ≤ 75_C)
Voc = 9.6 VDC
Isc = 3.5 mA
T5(Tamb ≤ 80_C)
Ca = 3.6 uF
T6(Tamb ≤ 75_C)
La = 100 mH
Po = 8.4 mW
T5(Tamb
− − −
T6(Tamb
T4(Tamb ≤ 125_C)
T5(Tamb ≤ 95_C)
T6(Tamb ≤ 80_C)
T4(Tamb ≤ 125_C)
T5(Tamb ≤ 95_C)
− − −
T6(Tamb ≤ 80_C)
Enclosure
Rating
Type 4X, IP66
Single Seal Device
Type 4X, IP66
Single Seal Device
Type 4X, IP66
Single Seal Device
≤
80_C)
Type 4X, IP66
≤
75_C)
Single Seal Device
Type 4X, IP66
Type 4X, IP66