Building Practice Requirements RBS 2000
43.1.3
Criteria for flame resistance of materials
ASTM Standard D 2863-77, Oxygen Index (OI)
Required Test result: OI >= 28
or
UL Standard 94 Vertical Burning Test for Classifying Materials.
Requirements according to specification in:
IEC 950, UL 1950, CSA C22.2 No. 950.
43.2

Poisonous Fumes

Apart from the inevitable carbon monoxide fumes and the possible HCl
(Hydrochloric acid) fumes there will be no other noxious, corrosive or
poisonous fumes in any harmful concentration during fire in Ericsson
equipment.
43.3
Declaration of Materials
Materials which are under legal restrictions are declared according to
relevant standards.
43.4
Silicone
The use of silicone products is restricted to the use of wiremesh silicone
rubber gasket for encloses of Ericsson equipment cabinets. The
wiremesh is applied as EMC protection.
43.5
Environmental Consideration during the Life-Cycle
According to "US Clean air act" Amendment Sect. 611. Label
requirements for Ozone-depleting substances, all products that are
manufactured using and containing the substance listed below shall be
marked in accordance to previous mentioned law. Products with
subunits manufactured using the substance below do not have to be
marked on higher level than subunit level.
Substance which Clean Air Act is applicable for:
CFC-11, CFC-12, CFC-13, CFC-111, CFC-112, CFC-113,CFC-114,
CFC-115, CFC-211,CFC-212, CFC-213, CFC-214, CFC-215, CFC-216,
CFC-217,Halon-1211, Halon-1301, Halon-2402, Carbon tetrachloride
(CT), Methyl- chloroform (1, 1, 1 - trichlororetane).