Weighing Functions
Name
Max. waiting time for
TIME
stand-still 1
Max. negative weight for
BYTE
zero setting when
switching on
Max. positive weight for
BYTE
zero setting when
switching on
Maximum negative
BYTE
weight for zero setting
Maximum positive weight
BYTE
for zero setting
Tare max. weight T-
BYTE
Load cell type
BYTE
Timeout digital LC
WORD
Regulations
STRING
[4]
Unit of measurement
STRING
[4]
Stand-still range 2
REAL
Stand-still time 2
TIME
Max. waiting time for
TIME
stand-still 2
Stand-still range 3
REAL
Stand-still time 3
TIME
Minimum waiting time at
TIME
stand-still 3
Smallest set weight ∑min REAL
Distribution value dt
REAL
5-44
Type
Address
Default
DBB100
2000
DBB104
10
DBB105
10
DBB106
1
DBB107
3
DBB108
100
DBB109
0
DBW110
240
DBB112
"----"
DBB118
kg
DBD124
0,02
DBB128
1000
DBB132
500
DBD136
0,02
DBB140
1000
DBB144
500
DBD148
100
Wizzard:
= WB
max
DBD152
0,1
Range of Values / Explanation
If there is no stand-still 1, the respective weighing
instruction will be rejected with an operational error
with a setting of 0 and otherwise, the waiting time
will elapse. If the max. waiting time has elapsed and
there is still no stand-still, an error message is sent.
For weighing instructions that are activated by an
operator, a setting around 2000 ms is reasonable.
(During the weighing cycle, this time is not
monitored)
Negative range for Switch-on zero setting device [in
% of weighing range
]
max
(Entry of Pos- + Neg. zero set value must not
exceed 20% with country code "OIML")
Positive range for Switch-on zero setting device [in
% of weighing range
]
max
(Entry of Pos- + Neg. zero set value must not
exceed 20% with country code "OIML")
Negative range for zero setting device [in % of
weighing range
]
max
(Entry of Pos- + Neg. zero set value must not
exceed 4% with country code "OIML")
Negative range for zero setting device [in % of
weighing range
]
max
(Entry of Pos- + Neg. zero set value must not
exceed 4% with country code "OIML")
Subtractive tare device range
[in % of WR
with multi-range scale]
max
[in % of WR
with multi-resolution scale]
1
(Value must not exceed 100%)
Range of the additive tare device
[in % of WB
, only a single range scale is permitted
1
in conjunction with regulation code "OIML"]
(Value must not exceed 250%)
0: analog load cell
1: METTLER TOLEDO type WM or WMH
2: WIPOTEC digital load cell
3: PESA digital load cell
>3: analog load cell
Timeout in ms for receiving the cyclic weight value
of the digital load cell
"OIML" : = Regulation Code OIML
"----": = No Regulation Code
Stand-still range 2 cm weight unit Effective when
starting a weighing procedure
msec
Max. waiting time for stand-still when starting a
weighing (ms)
0: No waiting time active
Stand-still range 3 cm weight unit Effective after
switching off fine current.
msec
Minimum waiting time at stand-still after switching
off fine signal (msec)
0 No waiting time active
Must only be entered with AWI totalizing operating
mode.
dt can correspond with the numerical step in WB
Re-
ference
5.2.25
5.2.26
5.2.27
5.2.28
5.2.29
5.2.30
5.2.31
5.2.32
5.2.33
5.2.34
5.2.35
5.2.36
5.2.37
5.2.38
5.2.39
5.2.40
5.2.41
5.2.42
nmax