Dr3 A Djustment P Arameter (Nawi, Awi) - Siemens SIWAREX FTA Device Manual

Weighing electronics for automatic scale
Table of Contents

Advertisement

Weighing Functions
5.2 DR3 Adjustment Parameter (NAWI, AWI)
The adjustment parameter must be tested for every weighing procedure and
changed if necessary.
The scale is basically defined using the adjustment parameters and by performing
the adjustments. In calibration operation, the data of the DR3 cannot be changed
after the calibration is complete.
Procedure:
o
Check all parameters and change if necessary.
o
Send DR3 to the scale
o
Perform scale adjustment
o
Receive DR3 from the scale
Name
Adjustment digits for
DINT
Adjustment zero 0
Adjustment digits for
DINT
Adjustment weight 1
Adjustment digits for
DINT
Adjustment weight 2
Adjustment digits for
DINT
Adjustment weight 3
Adjustment digits for
DINT
Adjustment weight 4
Adjustment weight 1
REAL
Adjustment weight 2
REAL
Adjustment weight 3
REAL
Adjustment weight 4
REAL
Characteristic value
BYTE
range
Filter sequence
BYTE
Type of low pass filters
BYTE
Limit frequency
BYTE
5-42
Type
Address
Default
DBD000
1.398.101
DBD004
15.379.113
DBD008
0
DBD012
0
DBD016
0
DBD020
50
DBD024
0
DBD028
0
DBD032
0
DBB036
0
DBB037
0
DBB038
0
DBB039
4
Range of Values / Explanation
24
0 to: 2
Other definitions not permitted.
24
0 to: 2
Other definitions not permitted.
24
0 to: 2
Other definitions not permitted.
24
0 to: 2
Other definitions not permitted.
24
0 to: 2
Other definitions not permitted.
> 0
Other definitions not permitted.
> 0
Other definitions not permitted.
> 0
Other definitions not permitted.
> 0
Other definitions not permitted.
1: Characteristic value to 1mV/V
2: Characteristic value to 2mV/V
4: Characteristic value to 4mV/V
Other definitions not permitted.
Bit 0 :
0: Averaging filter before digital filter
1: Digital filter before averaging filter
Bits 1 to 7 not set
0: critically damped
1: Bessel-Filter
2: Butterworth Filter
Other definitions not permitted.
0: No filter
1: fg = 20Hz
2: fg = 10Hz
3: fg = 5Hz
4: fg = 2Hz
5: fg = 1Hz
6: fg = 0,5Hz
7: fg = 0,2Hz
Re-
ference
5.2.1
5.2.1
5.2.1
5.2.1
5.2.1
5.2.1
5.2.1
5.2.1
5.2.1
5.2.2
5.2.3
5.2.4
5.2.5
SIWAREX FTA