Messages and Diagnostics
Error
Data and
No.
command errors -
description
149
Start not possible
since the
distribution memory
1 can overflow
150
Command
impossible since
SIMATIC CPU is in
STOP
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166-
Number format
175
error in data
record
166
Date Time
implausible
167
Time definition
implausible
168
Default percentage
value > 100%
7-148
Solution
Start not possible since the totalising of actual values in
distribution memory 1 overflowed in calibratable operation
(Specifications Code OIML in DR 3). Evaluate the distribution
memory and them delete them.
The command can only be executed in SIMATIC CPU RUN status.
This applies for the following commands (Codes):
Start a dosing procedure (100, 101, 102)
Step-on (103, 104)
Residual weighing (110)
Emptying on/off (109, 118)
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Data and time definition not plausible.
Correct the definition.
The following are allowed:
Year:
0..99
Month:
1..12
Day:
1..28/29/30/31
(depending on the month)
Hours:
0..23
Minutes:
0..59
Seconds:
0..59
Weekday:
1..7
The definition for a time definition is not plausible. Check the
following conditions:
DR3: Standstill times 1, 2 or 3 must be at least 100 msec
DR4: Timeout value for the log output monitor must be at least
1000 msec
DR23: Inching time must be greater than 0
DR23: The emptying time may not be greater than the maximum
emptying time
The percentage definition is greater than 100%. Decrease one of
the following entries.
SIWAREX FTA