Siemens SIWAREX FTA Device Manual page 144

Weighing electronics for automatic scale
Table of Contents

Advertisement

Commands
Code
Command explanation
Continue
103
Continue the weighing cycle. Weighing and
emptying are continued with this command.
104
Continue weighing with pulse dosing
Weighing is continued in pulse dosing operation
only (Pulse / Pause).
Stop (halt immediately) in weighing cycle
105
Stops immediately for weighing or emptying, the
scale stops and remains in "stopped" status.
Possible commands to follow:
103 – Continue
104 – Continue weighing with pulse dosing
108 – Abort
110 – Residual weighing
End continuous operation
106
The current weighing is completed and then the
continuous operation is ended.
Activate check stop
107
The scale is stopped at the next defined step for
the check stop. Continued with:
103 – Continue
104 – Continue weighing with pulse dosing
108 – Abort
110 – Residual weighing
Abort
108
The stopped weighing cycle is ended with no
further activity. No automatic emptying is
performed. The previous weight is not taken into
account in the totalising calculation.
Empty on
109
This command activates the emptying signal in
halted-state (no weighing cycle active) If the
emptying time is 0 then the emptying signal is
activated until the weight is in the empty range.
Independent from this, the emptying can be ended
with command 118.
6-132
Executable
in following
operating
states
Stopped
Stopped
Weighing cycle
Stopped,
weighing cycle
Not in service.
Stopped
No weighing
cycle
SIWAREX FTA

Advertisement

Table of Contents
loading

Table of Contents