HVAC Mode: enables or disables the sending of an HVAC special-mode
trigger value through object "[Ix] [Ci] Detection Status (HVAC)". The desired
HVAC mode can be set through parameter Value, which provides the
following options:
Sending Mode: sets whether the above values should be sent "Once" or be
"Cyclic". In case of selecting the latter, one more parameter will show up:
 Period: 1 to 255 seconds, 1 to 255 minutes, 1 to 18 hours.
Delay: sets the time that the device should wait before sending the values to
the bus, once the channel enters the Detection state. The available values
are 0 to 255 seconds, 0 to 255 minutes and 0 to 18 hours.

3.2.2 NO DETECTION

The options are analogous to those for Detection (section 3.2.1). The values will be
sent through the same objects in both cases (Detection and No Detection).
3.2.3 CHANNEL LOCK
While the channel remains locked, any further sendings to the bus related to that
channel will be interrupted, no matter if motion detections take place or not. It is
possible to start or end the lock state through a binary object ("[Ix][Ci] Lock") or a
scene object ("[Ix][Motion Detector] Scene Input]").
The parameters available for this function are:
http://www.zennio.com
HVAC Mode
Object Value
Comfort
1
Standby
2
Economy
3
Building Protection
4
Table 1. HVAC Modes
Technical Support:
Motion Detector
http://zennioenglish.zendesk.com