Operating manual
Message, cause and corrective measures
Insulation failure > Check generator
The inverter has detected a ground fault in the PV array.
Corrective measures:
• Check the PV system for ground faults (see Section 12.4, page 87).
Resid.curr.too.high > Check generator
The inverter has detected a residual current due to temporary grounding of the
PV array.
Corrective measures:
• Check the PV system for ground faults (see Section 12.4, page 87).
DC overcurrent > Check generator
Overcurrent at the DC input. The inverter briefly interrupts feed-in operation.
Corrective measures:
• If this message is displayed frequently, ensure that the PV array has been
correctly rated and wired.
Self diagnosis > Interference device
The cause must be determined by the Service.
Corrective measures:
• Contact the Service (see Section 16 "Contact", page 102).
Self-diagnosis > Overtemperature
The inverter has switched off due to excessive temperature.
Corrective measures:
• Clean the cooling fins on the rear of the enclosure and the air ducts on
the top using a soft brush.
• Ensure that the inverter has sufficient ventilation.
• Ensure that the ambient temperature +35°C has not been exceeded.
• Ensure that the inverter is not exposed to direct solar irradiation.
Minimum operating temperature not reached
The inverter will only recommence grid feed-in once the temperature has
reached at least −25°C.