Advertisement

5. Operation

5.5. Transmitter menu

5.5
Transmitter menu

Menu tree

At the PV display, press Enter to access the menus. To interact with the menus use the Device Local
Configuration onscreen buttons (page 30) or the buttons on your PDA.
Menu item
CAL
USER CAL
CAL RSTR
LPR CHK
RADIO
PRI RSSI
SEC RSSI
WFN ID
DEV ADD
TX POWER
26
OneWireless XYR 6000 SmartCET Corrosion Transmitter User's Manual

Table 8 Menu tree

Description
Calibration menu. May be password-protected. See Table 9 on page 30 for
password number entry.
Lets you set calibrate to custom low and high range values. See page 12.
Restores calibration to factory setting. The factory setting is very accurate
and should be adequate for most applications. See page 12.
Linear Polarization Resistance check. Use this to check a known applied
resistance. The displayed value should agree with the applied resistance; if
not then a problem exists in the probe or in the corrosion parameters. See
page 12.
Radio menu
Primary receive signal strength. Read only. Signal strength 00 is too weak to
connect to the network.
Displayed Value
Value dBm
00
< -86
01
-86 to -81
02
-80 to -75
03
-74 to -69
04
-68 to -63
05
-62 to -57
06
-56 to -51
07
-50 to -45
08
-44 to -11
09
≥ -10
Secondary receive signal strength. Same as PRI RSSI. Read only.
Wireless Field Network ID. Read only.
Device address. Read only.
Radio transmit power. Read only.
Rx Margin dB
< 10
10 to 15
16 to 21
22 to 27
28 to 33
34 to 39
40 to 45
46 to 51
52 to 85
Saturation
Revision 3
6/24/08