Advertisement

5. Operation
5.3. Transmitter PV display
Transmitter
Wireless Builder display
display
Blank
DAC Voltage Deviation
Blank
Calibration Cleared
blank*
Device/Firmware
Mismatch*
blank*
Heap Memory Not
Available*
blank*
Watchdog Timer Error*
24
OneWireless XYR 6000 SmartCET Corrosion Transmitter User's Manual
Definition
Electrode driver voltage
deviation > 3% of
measured voltage
User calibration cleared
to factory constants
Sensor Board Firmware
Error. The software did
not pass verification
tests.
Heap Allocation Failure.
Software detected heap
shortage and some
communication packets
may have been dropped.
Sensor Watchdog
Timeout. The processor
was restarted due to
unexpected operation.
What to do
Check electrodes for conductive
films.
Check transmitter probe cable
connections for a possible short at
the transmitter input terminals.
Check transmitter operation offline
with a different probe to determine
if the fault is caused by the probe
or transmitter.
User calibration has been cleared
and reset to the factory values.
Proceed with user calibration if
utilizing probe cables >12 ft and if
the anticipated corrosion rate is
>200 mpy.
Replace sensor module. See page
45.
Clear by warm restart of device. If
condition persists contact
Honeywell service.
Clear by warm restart of device. If
condition persists contact
Honeywell service.
Revision 3
6/24/08