5.5

Transmitter menu

Menu tree
At the PV display, press Enter to access the menus. To interact with the menus use the Device Local
Configuration onscreen buttons (page 31) or the buttons on your PDA.
Menu item
CAL
CH-1
CH-2
CH-3
RADIO
PRI RSSI
SEC RSSI
EXIT
Revision 1
January 2011
Table 8 Menu tree
Description
Calibration menu. May be password-protected. See Table 9 on
page 31 for password number entry.
Channel 1.
Channel 2.
Channel 3.
CAL RSTR
Restores selected channel to factory calibration.
USER CAL
Lets you calibrate selected channel's low and high points.
CAL CLR
Clear the factory and user calibration.
EXIT
Exits calibration menu and returns to PV display.
Radio menu
Primary receive signal strength. Read only. Signal strength 00 is too
weak to connect to the network.
Displayed Value
00
01
02
03
04
05
06
07
08
09
Secondary receive signal strength. Same as PRI RSSI. Read only.
Exit from Radio Menu
Value dBm
< -86
-86 to -81
-80 to -75
-74 to -69
-68 to -63
-62 to -57
-56 to -51
-50 to -45
-44 to -11
≥ -10
User's Manual
5. Operation
5.5. Transmitter menu
Rx Margin dB
< 10
10 to 15
16 to 21
22 to 27
28 to 33
34 to 39
40 to 45
46 to 51
52 to 85
Saturation
27