5. Operation

5.5. Transmitter menu

5.5
Transmitter menu

Menu tree

At the PV display, press Enter to access the menus. To interact with the menus use the Device Local
Configuration onscreen buttons (page 26) or the buttons on your PDA.
Menu item
CAL
CAL RESTR
USER CAL
CAL CLR
RADIO
PRI RSSI
SEC RSSI
WFN ID
DEV ADD
TX POWER
22

Table 9 Menu tree

Description
Calibration menu. May be password-protected. See Table 10 on page 26 for
password number entry. See page 10 for calibration details.
Constants for the channel 1 are restored to factory defaults.
Calibrates the channel to the low and high range values for selected input
type.
FACTORY or USER Calibration constants for the channel can be cleared.
Radio menu
Primary receive signal strength. Read only. Signal strength 00 is too weak to
connect to the network.
Displayed Value
00
01
02
03
04
05
06
07
08
09
Secondary receive signal strength. Same as PRI RSSI. Read only.
Wireless Field Network ID. Read only.
Device address. Read only.
Radio transmit power. Read only.
OneWireless XYR 6000 HLAI Transmitter R120 User's Manual
Value dBm
Rx Margin dB
< -86
< 10
-86 to -81
10 to 15
-80 to -75
16 to 21
-74 to -69
22 to 27
-68 to -63
28 to 33
-62 to -57
34 to 39
-56 to -51
40 to 45
-50 to -45
46 to 51
-44 to -11
52 to 85
≥ -10
Saturation
Revision 9
July 2011