Transmitter Connection Status; Table 5 Transmitter Connection Status - Honeywell XYR 6000 User Manual

Smartcet corrosion transmitter
Hide thumbs Also See for XYR 6000:
Table of Contents

Advertisement

5. Operation

5.2. Transmitter connection status

5.2
Transmitter connection status
Displayed
Definition
status
NO KEY
Transmitter needs a key from the
Authentication Device and is not transmitting.
NOT CONN
Transmitter is in between discovery attempts.
DISCOVER
Transmitter has not made a connection to a
Multinode and is in discovery (searching for a
connection to a Multinode). Transmitter will
automatically enter a power saving mode if it
cannot make a connection and will retry later.
SECURING
Transmitter has connected with the network
and is validating its key.
CONNECTD
For units with radio firmware build* 53 or
higher:
Transmitter has validated the key and has
made a secure connection with at least two
Multinodes. Transmitter should appear in
Wireless Builder as an uncommissioned
device.
For units with radio firmware build* 52:
Transmitter has validated the key and has
made a secure connection with at least one
Multinode. Transmitter should appear in
Wireless Builder as an uncommissioned
device.
NO REDUN
Appears only on units with radio firmware
build* 53 or higher. No redundancy, that is,
Transmitter has connected with only one
Multinode.
*Use the PDA to determine your radio firmware build number (page 21).
20
OneWireless XYR 6000 SmartCET Corrosion Transmitter User's Manual

Table 5 Transmitter connection status

What to do
Transmit a key to the transmitter. See page
28.
If Transmitter does not make a connection
within five minutes, do the following:
Check that Key is correct for the network
you are trying to join.
Check that Multinode(s) in the local area
are turned on and are already a secure
part of the network.
Check if KeyServer is active.
Check the KeyServer Event Log to see if
the Transmitter is actively trying to join.
Errors in the Event Log show that the
Transmitter is trying to join but that there
are problems. Consult the OneWireless
Wireless Builder documentation for
troubleshooting errors.
Wait for connection. If Transmitter does not
make a connection within five minutes, see
NOT CONN in this table.
Wait for connection. If Transmitter does not
make a connection within five minutes, see
NOT CONN in this table.
For units with radio firmware build* 53 or
higher: No action required.
For units with radio firmware build* 52:
Transmitter will periodically look for a
second Multinode in order to form a
redundant connection to the network. If
connected with only one Multinode Wireless
Builder will display a Secondary Multinode
Address of 0.
No action required. The Transmitter will
periodically look for a second Multinode in
order to form a redundant connection to the
network
Revision 3
6/24/08

Advertisement

Table of Contents
loading