Wiring Plan, Single Chamber Housing - Vega VEGABAR 66 Operating Instructions Manual

Submersible pressure transmitter with certec measuring cell
Table of Contents

Advertisement

5 Connecting to power supply
Electronics and terminal
compartment
24
3. Loop the connection cable through the cable entry on the housing
base
2)
Information:
The cable gland can be mounted in three positions each displaced
by 90°. Simply exchange the cable gland against the blind plug in the
suitable thread opening.
4. Connect the wire ends as described under "Single/Double cham-
ber housing" according to the numbering
5. Connect the screen to the internal ground terminal, connect the
outer ground terminal above on the housing to potential equalisa-
tion
6. Tighten the compression nut of the cable entry gland. The seal
ring must completely encircle the cable
7. Attach the mounting plate again and tighten the screws
The electrical connection of the sensor to the external housing is
finished.
5.3

Wiring plan, single chamber housing

The following illustrations apply to the non-Ex as well as to the Ex-ia
version.
5
4
Fig. 14: Electronics and terminal compartment, single chamber housing
1
Plug connector for VEGACONNECT (I²C interface)
2
Spring-loaded terminals for connection of the external indication VEGADIS
61
3
Ground terminal for connection of the cable screen
4
Spring-loaded terminals for Foundation Fieldbus connection
5
Simulation switch ("on" = simulation mode)
The connection cable comes pre-assembled. If necessary, shorten it to the
2)
requested length, cut the breather capillaries clean. Remove approx. 5 cm of
the cable mantle, strip approx. 1 cm insulation from the ends of the individual
wires. After shortening the cable, fasten the type plate with support back on
the cable.
Typ:
Bus
Display
1
2
5 6 7 8
VEGABAR 66 • Foundation Fieldbus
1
I ² C
2
3