6.3.9.3 Interval

Interval Time:
The time (in Seconds) selected between 2 measurements. It will automatically store the result.
Count:
The number of measurements to be taken.
When all measurements are taken, the system halts and discharges the Transformer.
Fix Interval Time:
Selects the interval time from Start Time instead of from the 1st measurement point.
e.g. If the Interval Time is set to 10 seconds and the first measurement is taken at 27 seconds, the
system stores results at 27, 37, 47...seconds if the check-box is not checked. If the check-box is
checked, the results will be taken and stored at 27, 30, 40, 50...seconds.
Note:
The current remains ON for the duration of the test and automatically stops after "Count" number of
measurements are taken.
Instruction Manual Winding Resistance Meter
Type WR100 / WR50 / WR14
Performs a selected number of measurements
(selected with "Count") and stores result.