Section 7: Foundation
Fieldbus
April 2017
Index
Parameter
Number Units
LO_PRI
52
MATH_FORM
73
MODE_BLK
05
OUT
09
OUT_HI_LIM
28
OUT-LO_LIM
29
OUT_SCALE
11
PV
07
PV_FTIME
16
PV_SCALE
10
RATE
26
RCAS_IN
32
RCAS_OUT
35
RESET
24
ROUT_IN
33
ROUT_OUT
36
SHED_OPT
34
SP
08
SP_FTIME
69
SP_HI_LIM
21
SP_LO_LIM
22
SP_RATE_DN
19
SP-RATE_UP
20
SP_WORK
68
STATUS_OPTS
14
STRATEGY
03
13
2
Description
None
The priority of the LO alarm.
None
Selects equation form (series or standard).
None
The actual, target, permitted, and normal modes of the block.
Target: The mode to "go to"
Actual: The mode the "block is currently in"
Permitted: Allowed modes that target may take on
Normal: Most common mode for target
EU of OUT SCALE
The block input value and status.
EU of OUT_SCALE
The maximum output value allowed.
EU of OUT_SCALE
The minimum output value allowed.
None
The high and low scale values, engineering units code, and number of
digits to the right of the decimal point associated with OUT.
EU of PV_SCALE
The process variable used in block execution.
Seconds
The time constant of the first-order PV filter. It is the time required for a
63 percent change in the IN value.
None
The high and low scale values, engineering units code, and number of
digits to the right of the decimal point associated with PV.
Seconds
The derivative action time constant.
EU of PV_SCALE
Target setpoint and status that is provided by a supervisory host. Used
when mode is RCAS.
EU of PV_SCALE
Block setpoint and status after ramping, filtering, and limiting that is
provided to a supervisory host for back calculation to allow action to be
taken under limiting conditions or mode change. Used when mode is
RCAS.
Seconds per repeat
The integral action time constant.
EU of OUT_SCALE
Target output and status that is provided by a supervisory host. Used
when mode is ROUT.
EU of OUT_SCALE
Block output that is provided to a supervisory host for a back calcula-
tion to allow action to be taken under limiting conditions or mode
change. Used when mode is RCAS.
None
Defines action to be taken on remote control device time-out.
EU of PV_SCALE
The target block setpoint value. It is the result of setpoint limiting and
setpoint rate of change limiting.
Seconds
The time constant of the first-order SP filter. It is the time required for a
63 percent change in the IN value.
EU of PV_SCALE
The highest SP value allowed.
EU of PV_SCALE
The lowest SP value allowed.
EU of PV_SCALE per
Ramp rate for downward SP changes. When the ramp rate is set to zero,
second
the SP is used immediately.
EU of PV_SCALE per
Ramp rate for upward SP changes. When the ramp rate is set to zero,
second
the SP is used immediately.
EU of PV_SCALE
The working setpoint of the block after limiting and filtering is applied.
None
Allows you to select options for status handling and processing. The
supported status option for the PID block is Target to Manual if Bad IN.
None
The strategy field can be used to identify grouping of blocks. This data
is not checked or processed by the block.
Instruction Manual
Proportional/ Integral/Derivative (PID) Function
Block
IM-106-880C, OI