Emerson Rosemount OCX8800 Instruction Manual page 142

Oxygen and combustibles transmitter, hazardous location probe with integral electronics
Hide thumbs Also See for Rosemount OCX8800:
Table of Contents

Advertisement

Section 7: Foundation
Fieldbus
April 2017
Index
Number Units
Parameter
HI_HI_LIM
26
HI_HI_PRI
25
HI_LIM
28
HI_PRI
27
IO_OPTS
13
L_TYPE
16
LO_ALM
35
LO_LIM
30
LO_LO_ALM
36
LO_LO_LIM
32
LO_LO_PRI
31
LO_PRI
29
LOW_CUT
17
MODE_BLK
05
OUT
08
OUT_D
37
OUT_SCALE
11
PV
07
PV_FTIME
18
SIMULATE
09
STRATEGY
03
ST_REV
01
TAG_DESC
02
UPDATE_EVT
20
VAR_INDEX
39
VAR_SCAN
40
XD_SCALE
10
116
Description
EU of PV_SCALE
The setting for the alarm limit used to detect the HI HI alarm condition.
None
The priority of the HI HI alarm.
EU of PV_SCALE
The setting for the alarm limit used to detect the HI alarm condition.
None
The priority of the HI alarm.
None
Allows the selection of input/output options used to alter the PV. Low
cutoff enabled is the only selectable option.
None
Linearization type. Determines whether the field value is used directly
(Direct), is converted linearly (Indirect), or is converted with the square
root (Indirect Square Root).
None
The LO alarm data, which includes a value of the alarm, a timestamp of
occurrence and the state of the alarm.
EU of PV_SCALE
The setting for the alarm limit used to detect the LO alarm condition.
None
The LO LO alarm data, which includes a value of the alarm, a timestamp
of occurrence and the state of the alarm.
EU of PV_SCALE
The setting for the alarm limit used to detect the LO LO alarm condi-
tion.
None
The priority of the LO LO alarm.
None
The priority of the LO alarm.
%
If percentage value of transducer input fails below this, PV = 0.
None
The actual, target, permitted, and normal modes of the block.
Target: The mode to "go to"
Actual: The mode the "block is currently in"
Permitted: Allowed modes that target may take on
Normal: Most common mode for target
EU of OUT_SCALE
The block output value and status.
None
Discrete output to indicate a selected alarm condition.
None
The high and low scale values, engineering units code, and number of
digits to the right of the decimal point associated with OUT.
EU of XD_SCALE
The process variable used in block execution.
Seconds
The time constant of the first-order PV filter. It is the time required for a
63% change in the IN value.
None
A group of data that contains the current transducer value and status,
the simulated transducer value and status, and the enable/disable bit.
None
The strategy field can be used to identify grouping of blocks. This data
is not checked or processed by the block.
None
The revision level of the static data associated with the function block.
The revision value will be incremented each time a static parameter val-
ue in the block is changed.
None
The user description of the intended application of the block.
None
This alert is generated by any change to the static data.
% of OUT Range
The average absolute error between the PV and its previous mean value
over that evaluation time defined by VAR_SCAN.
Seconds
The time over which the VAR_INDEX is evaluated.
None
The high and low scale values, engineering units code, and number of
digits to the right of the decimal point associated with the channel in-
put value.
The XD_SCALE units code must match the units code of the measure-
ment channel in the transducer block. If the units do not match, the
block will not transition to MAN or AUTO.
Instruction Manual
IM-106-880C, OI
Introduction