Cornelius Viper E 2 Flavor Service Manual page 73

Hide thumbs Also See for Viper E 2 Flavor:
Table of Contents

Advertisement

Compressor Running
but not Cooling
Restricted Air Flow
Fan Motor
Hot Gas Valve
No/Low Refrigerant
Sensors
© 2008-2016, Cornelius Inc.
A. Low refrigerant.
B. Restricted condenser/filter.
C. Condenser fan motor/blade defec-
tive.
D. Hot gas valve leaking or open.
E. Defective compressor.
A. Dirty filter.
B. Dirty condenser.
C. Damaged fins.
D. Not enough "clearance" around
unit.
A. Bad connection
B. Bad motor
C. Cracked or bent fan blade
A. Miswired.
B. Defective coil.
C. Defective product delivery board.
A. Leak.
A. Bad connection.
B. Bad sensor.
C. Sensor out of position.
D. Defective product delivery board.
- 67 -
Viper Service Manual
A. Repair leak and weigh in new
charge.
B. Clean or repair.
C. Repair or replace.
D. Replace.
E. Repair or replace.
A. Clean filter.
B. Clean condenser.
C. Repair/replace if necessary.
D. Ensure proper spacing around
unit.
A. Check/connect
B. Replace motor
C. Replace fan blade
A. Correct wiring.
B. Replace coil.
C. Replace.
A. Repair and weigh in new charge.
A. Correct wiring.
B. Replace sensor.
C. Reposition sensor and clip.
D. Replace.
Publication Number: 621260373SER