Figure 20. Return Water Or Outdoor Air Reset (Si) - McQuay MicroTech II Operation Manual

Chiller system manager (csm) hardwired chillers
Hide thumbs Also See for MicroTech II:
Table of Contents

Advertisement

Figure 20. Return Water or Outdoor Air Reset (SI)

For example, if the settings of the Figure 19 and Figure 20 are used, the following occurs when Outdoor Air reset is
selected:
Outdoor air temperature
55.0°F (12.5°C)
70.0°F (20.0°C)
85.0°F (27.5°C)
You can monitor the current return water and outdoor air temperatures on the Temperature screen.
Note: If communications are lost with a BAS that is supplying the outdoor air temperature to the CSM, the CSM retains
and uses the last temperature it received until communications are restored.
To set up Return Water or Outdoor Air reset
1.
Set the Chilled Water Temperature Reset Type variable to "Return Water" reset or "OAT".
2.
Set the following variables as required:
• Minimum System Setpoint
• Maximum System Setpoint
• Minimum System Setpoint At
• Maximum System Setpoint At
The CSM automatically resets the System Setpoint. You can ignore the remaining reset variables.
Note: To use the Outdoor Air reset method; an outdoor air temperature sensor must be connected to the CSM, received
from a BAS, or received from a chiller with an OAT sensor. To use the Return Water reset method; a return chilled water
temperature sensor must be connected to the CSM. For more information, see the Field Wiring section of IM 781.
Reset from an External Signal
When the external reset method is used, an external analog signal and the reset function determine the System Setpoint. See
Figure 21 and Figure 22. The following variables define the function: Minimum System Setpoint and Maximum System
Setpoint. The figures show typical values of these variables.
Page 54
12
11
Max System Spt= 12°C
10
9
8
Min System Spt= 7°C
7
Max Sys Spt At= 15°C
6
Min Sys Spt At= 25°C
5
10
15
20
Return Water or Outdoor Air Temperature (°C)
Corresponding System Setpoint
54.0°F (12.0°C)
49.0°F (9.5°C)
44.0°F (7.0°C)
25
30
a0149
OM 780-2