Return/Exhaust Fan Setup Menu

Table 28: Return/Exhaust Fan Setup Menu
Menu Display Name Item Display Name
Ret/Exh Fan Setup
BSP Ctrl Dly=
BSP DB=
BSP Period=
BSP Gain=
Max Spd Chg=
Sup Fan Max=
RF @ SF Max
Sup Fan Min=
RF @ SF Min=
Min Speed=
MinExStrtTime=
MinExStopTime=
MinExhOAPos=
MinExhSAFCap=
BSP Ctrl Delay is an adjustable item that sets the duration of time that the minimum speed
signal is sent to the VFD after the return fan is started via a digital output. Control reverts to
either building pressure or speed after the fan has been on for the BSPCtrlDelay (default 30
seconds).
BSP DB is an adjustable item which sets a dead band around the BldgSP Spt parameter. No
building static pressure control action is taken when the current building static pressure input
is within this dead band.
BSP Period is an adjustable item which sets the "sampling period" used in the PI control
function that modulates the return air or exhaust fan VFD.
BSP Gain is an adjustable item which sets the "gain" used in the PI control function that
modulates the return air or exhaust fan VFD.
Max Spd Chg is an adjustable item that sets the maximum value for a VFD speed increase or
decrease. This speed change (either a positive or negative value) is added to the current fan
speed whenever the building static pressure is outside of the deadband, and a counter exceeds
the sample time.
Sup Fan Max is an adjustable item used with the RF@SF Max parameter described below to
set the SAF/RAF tracking offset at the high end.
RF@SF Max is an adjustable item that sets the speed of the return/exhaust fan when the
supply fan is at the Sup Fan Max value.
Sup Fan Min is an adjustable item used with the RF@SF Min parameter described below to
set the SAF/RAF tracking offset at the low end.
RF@SF Min is an adjustable item that sets the maximum speed of the return/exhaust fan
when the supply fan is at its minimum speed.
Min Speed is an adjustable item the sets the minimum speed of the RF/EF fan.
MinExStrtTime is an adjustable item that sets the Minimum Exhaust Fan On Time (Default =
120 seconds).
MinExStopTime is an adjustable item that sets the Minimum Exhaust Fan Stop Time (Default
= 120 seconds).
MinExhOAPos is an adjustable item that sets the Minimum Exhaust OA Position (default
5%). %). The outdoor air dampers must be open more that this value for prop exhaust fan
operation.
MinExhSAFCap is an adjustable item that sets the Minimum Exhaust SAF capacity (default
10%). The supply air fan speed must be higher than this value for prop exhaust fan operation.
Default Setting
Range
30s
0-999s
0.01in
0.0-0.1in
5s
0-999s
0.2
0.0-100.0s
4%
0-100%
100%
0-100%
95%
0-100%
30%
0-100%
25%
0-100%
5%
0-100%
120s
60-300s
120s
60-300s
5%
0-100%
10%
0-100%
Password Level
4
4
4
4
4
4
4
4
4
4
4
4
4
4