List Of Remote Commands; List Of "Set" Commands - EMS EkoMini Operator's Manual

Hide thumbs Also See for EkoMini:
Table of Contents

Advertisement

Note: Before logging off the unit, it is advisable to test the configuration. By
issuing a test report 1 command, the unit will log the user off and try to send an
alarm code to the Report 1. If there are no alarms, it will send a 0.
4.7

List of Remote Commands:

These commands allow the user to observe repeater parameters:
MENU = Displays List of Commands
HELP = Displays List of Commands And Help Formatting
EVNT = Displays User Alarm Log
CONF = Displays Basic Configuration
RPRT = Displays Report Alarms Settings
KPAL = Displays KeepAlive settings, described in Section 4.9 below
TEST REPORT # = Will log off user and attempt to page report # with alarm
cleared code.
Enter KADIAL to test the Keep Alive Number. Example (TEST REPORT
KADIAL)
4.8

List of "SET" Commands:

These commands allow the user to change repeater parameters:
RP # DIAL = Report (#=1,2,3) Dial out Number. 20 digits
RP # PINN = Report (#=1,2,3) Pin Number. 10 digits
RP # DLAY = Report (#=2,3) Dial Delay (minutes) from Previous Report. 0-999
RP ACTV = Report Active. Yes or No
RP TYPE = Reporting Unit Type? Name or Number(serial)
PW 1 = Password 1 change. 5 Characters or Numbers (supervisor's password)
PW 2 = Password 2 change. 5 Characters or Numbers
PW 3 = Password 3 change. 5 Characters or Numbers
UN = Unit Name Change. 10 Characters. Default is Serial Number
AR = Answer Rings. 0-999. Default = 2
TM = System time; Format: 01:31:29 for 1:31 am or 13:31:29 for 1:31 pm
DT = System date; Format: 01/10/99 for Jan 10, 1999
EMS Wireless EkoMini Manual