5 SETTINGS
The disturbance detector responds to the change in currents of twice the current cut-off level. The default cut-off threshold
is 0.02 pu; thus by default the disturbance detector responds to a change of 0.04 pu. The metering sensitivity setting (

UCT SETUP
DISPLAY PROPERTIES
accordingly.
EXAMPLE USE OF SOURCES:
An example of the use of sources is shown in the diagram below. A relay could have the following hardware configuration:
This configuration could be used on a two-winding transformer, with one winding connected into a breaker-and-a-half sys-
tem. The following figure shows the arrangement of sources used to provide the functions required in this application, and
the CT/VT inputs that are used to provide the data.
Y LV
SRC 1
Phase CT
M1
Ground CT
M1
Phase VT
M5
Aux VT
None
GE Multilin

CURRENT CUT-OFF LEVEL
Figure 5–20: EXAMPLE USE OF SOURCES
D HV
AUX
SRC 2
SRC 3
F1+F5
None
None
None
None
None
None
U1
F60 Feeder Protection System
) controls the sensitivity of the disturbance detector
5.4 SYSTEM SETUP
PROD-
5
5-77