3.2 WIRING
3
The phase voltage channels are used for most metering and protection purposes. The auxiliary voltage channel is used as
input for the synchrocheck and volts-per-hertz features.
Substitute the tilde "~" symbol with the slot position of the module in the following figure.
NOTE
3-14
UNSHIELDED CABLE
Ground connection to neutral
must be on the source side
Source
A
B
C
N
LOAD
Figure 3–15: ZERO-SEQUENCE CORE BALANCE CT INSTALLATION
Current inputs
8F and 8G modules (4 CTs and 4 VTs)
8H and 8J modules (8 CTs)
Current inputs
8Z module (used for high-impedance fault detection)
Figure 3–16: CT/VT MODULE WIRING
F60 Feeder Protection System
G
Ground
outside CT
Voltage inputs
Current inputs
Not used
3 HARDWARE
SHIELDED CABLE
Stress cone
Source
shields
A
B
C
To ground;
LOAD
must be on
load side
996630A5
842769A1.CDR
GE Multilin