7.2 TARGETS
How often the test is performed: Module dependent.
What to do: Contact the factory and supply the failure code noted in the display. The "xxx" text identifies the failed mod-
ule (for example, F8L).
IEC 61850 DATA SET:
LLN0 GOOSE# Error
Latched target message: No.
Description of problem: A data item in a configurable GOOSE data set is not supported by the F60 order code.
How often the test is performed: On power up
What to do: Verify that all the items in the GOOSE data set are supported by the F60. The EnerVista UR Setup soft-
ware will list the valid items. An IEC61850 client will also show which nodes are available for the F60.
IEC 61850 DATA SET:
LLN0 BR# Error
Latched target message: No.
Description of problem: A data item in a configurable report data set is not supported by the F60 order code.
How often the test is performed: On power up
What to do: Verify that all the items in the configurable report data set are supported by the F60. The EnerVista UR
Setup software will list the valid items. An IEC61850 client will also show which nodes are available for the F60.
MAINTENANCE ALERT:
Replace Battery
Latched target message: Yes.
Description of problem: The battery is not functioning.
How often the test is performed: The battery is monitored every five seconds. The error message displays after 60 sec-
onds if the problem persists
What to do: Return the power supply module to GE Digital Energy for battery replacement.
MAINTENANCE ALERT:
7
Direct I/O Ring Break
Latched target message: No.
Description of problem: Direct input and output settings are configured for a ring, but the connection is not in a ring.
How often the test is performed: Every second
What to do: Check direct input and output configuration and wiring.
MAINTENANCE ALERT:
ENET MODULE OFFLINE
Latched target message: No.
Description of problem: The F60 has failed to detect the Ethernet switch.
How often the test is performed: Monitored every five seconds. An error is issued after five consecutive failures
What to do: Check the F60 device and switch IP configuration settings. Check for incorrect UR port (port 7) settings on
the Ethernet switch. Check the power to the switch.
MAINTENANCE ALERT:
ENET PORT # OFFLINE
7-8
.
.
.
.
F60 Feeder Protection System
7 COMMANDS AND TARGETS
.
GE Multilin