Display; Breaker Control - GE F60 Instruction Manual

Ur series feeder protection system
Hide thumbs Also See for F60:
Table of Contents

Advertisement

4.2 FACEPLATE INTERFACE
4.
Slide the new user-programmable pushbutton label inside the pocket until the text is properly aligned with the buttons,
as shown below.
4
All messages are displayed on a 2 × 20 backlit liquid crystal display (LCD) to make them visible under poor lighting condi-
tions. While the keypad and display are not actively being used, the display will default to user-defined messages. Any high
priority event driven message will automatically override the default message and appear on the display.
a) INTRODUCTION
The F60 can interface with associated circuit breakers. In many cases the application monitors the state of the breaker,
which can be presented on faceplate LEDs, along with a breaker trouble indication. Breaker operations can be manually
initiated from faceplate keypad or automatically initiated from a FlexLogic™ operand. A setting is provided to assign names
to each breaker; this user-assigned name is used for the display of related flash messages. These features are provided for
two breakers; the user may use only those portions of the design relevant to a single breaker, which must be breaker 1.
For the following discussion it is assumed the
setting is "Enabled" for each breaker.
FUNCTION
b) CONTROL MODE SELECTION AND MONITORING
Installations may require that a breaker is operated in the three-pole only mode (3-pole), or in the one and three-pole (1-
pole) mode, selected by setting. If the mode is selected as three-pole, a single input tracks the breaker open or closed posi-
tion. If the mode is selected as one-pole, all three breaker pole states must be input to the relay. These inputs must be in
agreement to indicate the position of the breaker.
For the following discussion it is assumed the
1(2) PUSH BUTTON CONTROL
c) FACEPLATE (USER KEY) CONTROL
After the 30 minute interval during which command functions are permitted after a correct command password, the user
cannot open or close a breaker via the keypad. The following discussions begin from the not-permitted state.
d) CONTROL OF TWO BREAKERS
For the following example setup, the (Name) field represents the user-programmed variable name.
4-22
SETTINGS

SETTINGS
setting is "Enabled" for each breaker.
F60 Feeder Protection System


SYSTEM SETUP
BREAKERS

SYSTEM SETUP
BREAKERS
4 HUMAN INTERFACES

4.2.4 DISPLAY

4.2.5 BREAKER CONTROL

BREAKER 1(2)
BREAKER

BREAKER 1(2)
BREAKER
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents