GE F60 Instruction Manual page 289

Ur series feeder protection system
Hide thumbs Also See for F60:
Table of Contents

Advertisement

5 SETTINGS
Table 5–22: QUANTITIES FOR "MEASURED IG" CONFIGURATION
POLARIZING MODE
DIRECTION
Voltage
1
-- - VAG
(
where:
V_0
VBG
=
+
3
1
1
-- - IN
-- - IA
(
I_0
=
=
+
3
3
ECA = element characteristic angle and IG = ground current
When
NEUTRAL DIR OC1 POL VOLT
figure explains the usage of the voltage polarized directional unit of the element.
The figure below shows the voltage-polarized phase angle comparator characteristics for a phase A to ground fault, with:
ECA = 90° (element characteristic angle = centerline of operating characteristic)
FWD LA = 80° (forward limit angle = the ± angular limit with the ECA for operation)
REV LA = 80° (reverse limit angle = the ± angular limit with the ECA for operation)
The element incorporates a current reversal logic: if the reverse direction is indicated for at least 1.25 of a power system
cycle, the prospective forward indication is delayed by 1.5 of a power system cycle. The element is designed to emulate an
electromechanical directional device. Larger operating and polarizing signals results in faster directional discrimination
bringing more security to the element operation.
The forward-looking function is designed to be more secure as compared to the reverse-looking function, and therefore,
should be used for the tripping direction. The reverse-looking function is designed to be faster as compared to the forward-
looking function and should be used for the blocking direction. This allows for better protection coordination.
The above bias should be taken into account when using the neutral directional overcurrent element to directionalize other
protection elements.
REV Operating
Region
–ECA line
–3I_0 line
VCG
Figure 5–67: NEUTRAL DIRECTIONAL VOLTAGE-POLARIZED CHARACTERISTICS
GE Multilin
DIRECTIONAL UNIT
COMPARED PHASORS
–V_0 + Z_offset × IG/3
Forward
–V_0 + Z_offset × IG/3
Reverse
)
VCG
zero sequence voltage
+
=
)
IB
IC
zero sequence current
+
=
is set to "Measured VX", one-third of this voltage is used in place of V_0. The following
REV LA
–3V_0 line
line
LA
LA
REV LA
3V_0 line
line
F60 Feeder Protection System
IG × 1∠ECA
–IG × 1∠ECA
,
,
FWD LA
line
VAG
(reference)
FWD Operating
LA
ECA
LA
VBG
FWD LA
line
5.6 GROUPED ELEMENTS
OVERCURRENT UNIT
I
= |IG|
op
Region
3I_0 line
ECA line
827805A1.CDR
5-149
5