5.7 CONTROL ELEMENTS

PATH: SETTINGS
CONTROL ELEMENTS
 COUNTER 1
5
There are 8 identical digital counters, numbered from 1 to 8. A digital counter counts the number of state transitions from
Logic 0 to Logic 1. The counter is used to count operations such as the pickups of an element, the changes of state of an
external contact (e.g. breaker auxiliary switch), or pulses from a watt-hour meter.
COUNTER 1 UNITS: Assigns a label to identify the unit of measure pertaining to the digital transitions to be counted.
The units label will appear in the corresponding actual values status.
COUNTER 1 PRESET: Sets the count to a required preset value before counting operations begin, as in the case
where a substitute relay is to be installed in place of an in-service relay, or while the counter is running.
COUNTER 1 COMPARE: Sets the value to which the accumulated count value is compared. Three FlexLogic™ output
operands are provided to indicate if the present value is 'more than (HI)', 'equal to (EQL)', or 'less than (LO)' the set
value.
COUNTER 1 UP: Selects the FlexLogic™ operand for incrementing the counter. If an enabled UP input is received
when the accumulated value is at the limit of +2,147,483,647 counts, the counter will rollover to –2,147,483,648.
COUNTER 1 DOWN: Selects the FlexLogic™ operand for decrementing the counter. If an enabled DOWN input is
received when the accumulated value is at the limit of –2,147,483,648 counts, the counter will rollover to
+2,147,483,647.
COUNTER 1 BLOCK: Selects the FlexLogic™ operand for blocking the counting operation. All counter operands are
blocked.
5-210


DIGITAL COUNTERS

COUNTER 1
FUNCTION: Disabled
COUNTER 1 NAME:
MESSAGE
Counter 1
COUNTER 1 UNITS:
MESSAGE
COUNTER 1 PRESET:
MESSAGE
COUNTER 1 COMPARE:
MESSAGE
COUNTER 1 UP:
MESSAGE
Off
COUNTER 1 DOWN:
MESSAGE
Off
COUNTER 1 BLOCK:
MESSAGE
Off
CNT1 SET TO PRESET:
MESSAGE
Off
COUNTER 1 RESET:
MESSAGE
Off
COUNT1 FREEZE/RESET:
MESSAGE
Off
COUNT1 FREEZE/COUNT:
MESSAGE
Off
F60 Feeder Protection System
COUNTER 1(8)
Range: Disabled, Enabled
Range: 12 alphanumeric characters
Range: 6 alphanumeric characters
Range: –2,147,483,648 to +2,147,483,647
0
Range: –2,147,483,648 to +2,147,483,647
0
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
5 SETTINGS
5.7.11 DIGITAL COUNTERS